Discon(nect) screens, Fx sell screen, Stop sell reasons – Outback Power Systems MATE2 User Manual

Page 46

Advertising
background image



STATUS/FX/DISCON-----------P00

acin freq No

too high
DOWN STATUS PORT

STATUS/FX/DISCON-----------P00

acin voltage No

> max
DOWN UP TOP PORT

STATUS/FX/DISCON----------P00

acin freq No

too low
DOWN UP TOP PORT

STATUS/FX/DISCON-----------P00

acin voltage No

< min
DOWN UP TOP PORT

STATUS/FX/PAGE3----------------

choose category:

PG2 DISCON SELL MAIN

STATUS/FX/DISCON----------------

end of DISCON menu

UP TOP STATUS

DISCON(NECT) Screens

DISCON(NECT) Screens

acin freq too high: screen displays “Yes” if the AC source exceeds 69 Hz and the FX disconnects from

the source

acin freq too low: displays “Yes” if the FX disconnects from an AC source below 51 Hz

acin voltage > max: the source of the AC voltage exceeds the FX maximum of 140 VAC(default value)

acin voltage < min: the source of the AC voltage falls below the FX minimum of 108 VAC (default)

STATUS/FX/PAGE3-----------------

choose category:

PG2 DISCON SELL MAIN

STATUS/FX/PAGE3-----------------

choose category:

PG2 DISCON SELL MAIN

STATUS/FX/SELL------------- stop

sell 15

reason

STATUS PORT

Press STATUS to return to the

MAIN Menu.

Press MAIN to return to the

STATUS Menu

FX SELL Screen

stop sell reason: displays a numerical value

(15 in sample screen shown here) indicating

a reason a grid-tied FX has stopped selling

power to the utility grid; this screen is used

for troubleshooting by OutBack Power System

technicians.

Stop SELL Reasons

0

1

2 Island-detected wobble

3

4

5 Charge diode battery volt fault

6

7 Silent command

8 Save command

9 R60 off at go fast

10 R60 of at do relays

11 Current limit sell

12 Current limit charge

13

14 Back feed

15 Brute sell charge VAC over

Advertising