• When an OutBack HUB is employed, the GEN START CONTROL only affects the FX

programmed as the AGS PORT in the AGS setup. This is the HUB Port connected to the

FX with the generator start relay.

<OFF> manually overrides AGS mode. Pressing <OFF> brings up MAN-OFF indicating the

user manually shut off the generator.

<AUTO> allows the MATE to automatically start and stop the generator according to the

settings programmed in the AGS menu. Pressing <AUTO> brings up either AUTO-OFF or

AUTO-ON depending on the FX programming.

<ON> manually overrides AGS mode. Pressing it brings up MAN-ON indicating the user

manually turned the generator ON)

<OK> Returns to the point in the menu system where you entered the GEN START

CONTROL screen.

AC INPUT CONTROL

currently: USE

DROP USE OK

PRESS TWICE:

• The GEN START CONTROL screen allows

changes to the Advanced Generator Start

(AGS) mode.

• The AGS settings only take effect when

Advanced Generator Start is enabled (See the

AGS Mode section for more information).

NOTE: This does not control the GenAlert

function.

NOTE: To reset an AGS error, press <OFF> and then press <AUTO>.

PRESS THREE TIMES:

CHARGER CONTROL

currently:

OFF

OFF AUTO ON OK

• The CHARGER CONTROL screen appears.

• This allows the operation of the FX battery

charger to be preset for an available AC source.

• When an OutBack HUB is employed, the

CHARGER CONTROL only affects the Master

FX connected to PORT 1. The Master FX then

gives the same command to all slave FXs.