Outback Power Systems MATE2 User Manual
Page 53
• When an OutBack HUB is employed, the GEN START CONTROL only affects the FX
programmed as the AGS PORT in the AGS setup. This is the HUB Port connected to the
FX with the generator start relay.
<OFF> manually overrides AGS mode. Pressing <OFF> brings up MAN-OFF indicating the
user manually shut off the generator.
<AUTO> allows the MATE to automatically start and stop the generator according to the
settings programmed in the AGS menu. Pressing <AUTO> brings up either AUTO-OFF or
AUTO-ON depending on the FX programming.
<ON> manually overrides AGS mode. Pressing it brings up MAN-ON indicating the user
manually turned the generator ON)
<OK> Returns to the point in the menu system where you entered the GEN START
CONTROL screen.
AC INPUT CONTROL
currently: USE
DROP USE OK
PRESS TWICE:
• The GEN START CONTROL screen allows
changes to the Advanced Generator Start
(AGS) mode.
• The AGS settings only take effect when
Advanced Generator Start is enabled (See the
AGS Mode section for more information).
NOTE: This does not control the GenAlert
function.
NOTE: To reset an AGS error, press <OFF> and then press <AUTO>.
PRESS THREE TIMES:
CHARGER CONTROL
currently:
OFF
OFF AUTO ON OK
• The CHARGER CONTROL screen appears.
• This allows the operation of the FX battery
charger to be preset for an available AC source.
• When an OutBack HUB is employed, the
CHARGER CONTROL only affects the Master
FX connected to PORT 1. The Master FX then
gives the same command to all slave FXs.