Dvrt41direct vent gas fireplace, Twist lock pipes, How to use the vent graph – Vermont Casting DVRT41 User Manual

Page 13: Rear wall vent application

Advertising
background image

13

DVRT41Direct Vent Gas Fireplace

10006740

Male End

Female
End

Screw Holes

TWL100

Fig. 17 Twist-Lock pipe joints.

Twist Lock Pipes

When using twist lock pipe it is not necessary to use
sealant on the joints. The only areas of the venting
system that need to be sealed with high temperature
silicone sealant are the collars on the fireplace and
termination, and the sliding joint of any telescopic vent
section used in the system.

To join twist lock pipes together, simply align the beads
of the male end with the grooves of the female end,
twisting the pipe until the flange on the female end
contacts external flange on the male end. It is recom-
mended that you secure the joints with three (3) sheet
metal screws, however, this is not mandatory with twist
lock pipe. (Fig. 17)

To make it easier to assembly the joints, we suggest
putting a lubricant (Vaseline or similar) on the male end
of the twist lock pipe prior to assembly.

How to Use the Vent Graph

The Vent Graph should be read in conjunction with the
following vent installation instructions to determine the
relationship between the vertical and horizontal dimen-
sions fo the vent system.

1. Determine the height of the center of the horizontal

vent pipe exiting through the outer wall. Using this
dimension on the Sidewall Vent Graph (Fig. 17),
locate the point intersecting with the slanted graph
line.

2. From the point of this intersection, draw a vertical

line to the bottom of the graph.

3. Select the indicated dimension, and position the

fireplace in accordance with same.

EXAMPLE

A:

If the vertical dimension from the floor of the unit is 11’
(3.4m) the horizontal run to the face of the outer wall
must not exceed 14’ (4.3m).

EXAMPLE B:

If the vertical dimension from the floor of the unit is 7’
(2.1m), the horizontal run to the face of the outer wall
must not exceed 8

¹⁄₂

’ (2.6m).

Refer to Page 19 for venting

requirements for snorkels.

Vertical dimension from the floor of the unit

to the center of the horizontal vent pipe

Fig. 18 Sidewall venting graph. (Dimensions in feet.)

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

eg: A

eg: B

Horizontal dimension from the outside face of the wall to the

center of the fireplace vent flange

When installed as a rear vent unit this appliance may be
vented directly to a termination located on the rear wall
behind the appliance.

Only CFM Corporation venting components are
approved to be used in these applications (See
‘Venting Components’ listed for different installation
requirements).

The maximum horizontal distance between the rear
of the appliance (or end of the transition elbow in a
corner application) and the outside face of the rear
wall is 20” (508mm). (Fig. 19, 20)

Only one 45

°

elbow is allowed in these installations.

Minimum clearances between vent pipe and com-
bustible materials are as follows:

Top - 2" (51 mm)
Sides - 1" (25 mm)
Bottom - 1" (25 mm)

Rear Wall Vent Application

Advertising