D
GB
F
E

17

96031-02.2015-DGbF

Operation mode: The oil sump heater operates when the compressor is shut down.
The oil sump heater is switched off when the compressor starts.

Connexion: The oil sump heater must be connected via an auxiliary contact (or parallel wired auxiliary
contact) of the compressor contactor to a seperate electric circuit.
Electrical data: 110 - 240 V - 1 - 50/60 Hz, 50 - 120 W, PTC-heater adjusting.

5| Electrical connection

The compressor and the trigger unit MP10 are operational when the H3 LED (green) lights.

5.6 Function test of the trigger unit MP 10

Pos

Procedure

LED H1 LED H2 LED H3

red

red

green

1 Interrupt power supply (L1 or S1)

OFF

OFF

OFF

Release the motor temperature sensor connection (1 or 2)

Release the hot gas temperature sensor (if installed) (3 or 4)

2 Restore the power supply (L1 or S1)

ON

Function check of motor temperature sensor: operational

ON

Function check of hot gas temperature sensor: operational

ON

3

Interrupt power supply again (L1 or S1)

OFF

OFF

OFF

Reconnect terminals 1 or 2 and/or 3 or 4

4

Restore the power supply (L1 or S1):

OFF

OFF

ON

MP 10 is operational again

Before start-up, troubleshooting or making changes to the control power circuit, check the functionality
of the trigger unit:

ATTENTION! The oil sump heater must generally be connected and operated.

5.8 Ventilator motor

The ventilator motor for cooling the compressor is already wired in the terminal box. Please consult
the main-line wiring diagram in the terminal box for the power supply and triggering via the com-
pressor contactor. The ventilator motor is protected by a pressure controller.
Electrical data: 230 V / 1 / 50...60 Hz, 140 W, 0,71 A

5.7 Oil sump heater (accessories)

In order to avoid damage to the compressor, the compressor must be equipped with an oil sump
heater.