3 | areas of application – GEA Bock HAX2 CO2 T User Manual

Page 8

Advertising
background image

8

D
GB
F
E

96031-02.2015-DGbF

3 | Areas of application

ATTENTION! Compressor operation is possible within the operating limits

shown in the diagrams. Thresholds should not be selected as
design or continuous operation points.

- Max. permissible ambient temperature 45°C

- Max. permissible discharge end temperature 160°C.

- Max. permissible switching frequency 12x /h.

- A minimum running time of 3 min. steady-state condition

(continuous operation) must be achieved.

The compressors are filled at the factory with the following oil type:

GEA Bock C 85 E (only this oil may be used).

3.1 Refrigerants

CO

2

: R744

3.2 Oil charge

3.3 Limits of application

Max. permissible operating

pressure (LP/HP)

1)

: 100/150 bar

The oil level must be in the
visible part of the sight
glass; damage to the com-
pressor is possible if over-
filled or underfilled!

max. oil level

min. oil level

ATTENTION!

Fig. 4

1)

LP = Low pressure

HP = High pressure

Fig. 5

t

o

Evaporation temperature (°C)

∆t

oh

Suction gas superheat (K)

p

o

Suction pressure (bar)

p

v

2

Discharge end pressure (bar)

1

1 HAX2/130-4 CO

2

T

Applications limit

Unlimited

application range

Advertising