Benchmark 2.0ln low nox boiler, Gf-120 – AERCO BMK 1.5 LN October 2012 User Manual

Page 116

Advertising
background image


APPENDIX A

Benchmark 2.0LN Low NOx Boiler

GF-120

MENU ITEMS Installation, Operation and Maintenance Manual

OMM-0041_0E

Page 116 of 166 AERCO International Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288 PR1:10/18/12

Table A-1: Boiler Menu Item Descriptions-Continued

MENU LEVEL & OPTION

DESCRIPTION

TUNING MENU

Prop Band

Generates a fire rate based on the error that exists
between the setpoint temperature and the actual
outlet temperature. If the actual error is less than
the proportional band setting (1 to 120°F), the fire
rate will be less than 100%. If the error is equal to
or greater than the proportional band setting, the
fire rate will be 100%.

Integral Gain

This sets the fraction of the output, due to setpoint
error, to add or subtract from the output each
minute to move towards the setpoint. Gain is
adjustable from 0.00 to 1.00 (Default is 0.10).

Derivative Time

This value (0.0 to 20.0 min.) responds to the rate of
change of the setpoint error. This is the time that
this action advances the output.

WARMUP: The feature embodied in the following three menu items eliminates
Temperature Overshoots during the “Warmup” period of a cold ignition cycle on all
boilers by temporarily modifying the PID Gain parameter during warmup and for a period
defined in the Tuning Menu

Warmup Prop Band

Range = 1-120

Default = 95

Warmup Int Gain

Range = 1-200

Default = 50

Warmup PID Timer

Range = 1-240

Default = 20

Defaults?

Allows Tuning Menu options to be reset to their
Factory Default values.