Table E-1: Boiler Default Settings (Continued)

MENU & OPTION

FACTORY DEFAULT

Pump Delay Timer

0 min

Aux Start On Dly

0 sec

Failsafe Mode

Shutdown

Analog Output

Valve Position 0-10V

CAUTION: DO NOT Change

Lo Fire Timer

2 sec

Setpt Limit Band (If Setpt Limiting = Enabled)

5°F

Configuration Menu --Continued

Network Timeout

30 seconds

Hi DB Setpt En

30

Demand Offset

10

Deadband High

2

Deadband Low

2

Tuning Menu

Prop Band

70°F

Integral Gain

1.00

Derivative Time

0.0 min