Benchmark 2.0ln low nox boiler, Gf-123 – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual
Page 134
Advertising
Appendix E
Benchmark 2.0LN Low NOx Boiler
GF-123
Default Settings Installation, Operation and Maintenance Manual
OMM-0046_0E
Page 134 of 170
AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 08/20/12
Table E-1: Boiler Default Settings (Continued)
MENU & OPTION
FACTORY DEFAULT
Pump Delay Timer
0 min
Aux Start On Dly
0 sec
Failsafe Mode
Shutdown
Analog Output
Valve Position 0-10V
CAUTION: DO NOT Change
Lo Fire Timer
2 sec
Setpt Limit Band (If Setpt Limiting = Enabled)
5°F
Configuration Menu --Continued
Network Timeout
30 seconds
Hi DB Setpt En
30
Demand Offset
10
Deadband High
2
Deadband Low
2
Tuning Menu
Prop Band
70°F
Integral Gain
1.00
Derivative Time
0.0 min