2 rsi regulator calibration, Benchmark 2.0ln low nox boiler, Gf-123 – AERCO BMK 2.0 LN Natural Gas (SN G-11-1861 and above) User Manual

Page 88

Advertising
background image

Chapter 7

Benchmark 2.0LN Low NOx Boiler

GF-123

Maintenance

Installation, Operation and Maintenance Manual

OMM-0046_0E

Page 88 of 170

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 08/20/12

7.4.1.2 RSI Regulator Calibration

RSI regulator calibration is performed as follows:

1. Ensure that gas supply shut-off valve upstream of the unit is still turned OFF.

2. Turn OFF electrical power to the system.

3. CLOSE the following valves in the unit’s gas train (refer to Figure 7-4):

• RSI Gas Supply Valve

• RSI Bleed-off Valve

• Manual Shut-off Valve (between the Air/Fuel Valve and the SSOV).

4. Remove the pipe plug from the 1/4” NPT port on the outlet side of the RSI regulator, insert

NPT-to-barbed adapter fitting, and insert tube from the 16” w.c. manometer.

5. Remove the cap from the RSI Pressure Regulator and rotate the regulator adjustment

(beneath cap) counter-clockwise (CCW) to its lowest possible pressure setting that will allow
the cap to be installed.

6. OPEN the main gas supply upstream of the unit.

7. Turn ON electrical power to the system.

8. Slowly OPEN the RSI Gas Supply Valve and observe the reading on the manometer. It

should have a reading of less than 8.0” w.c.

9. Start the boiler in MANUAL Mode. Observe the manometer pressure when the RSI solenoid

“clicks” open after purge. The manometer should now provide a reading of less than 5.0”
w.c.

10. Look into the observation port in the top head and ensure that you observe the orange glow

of the RSI flame during the ignition trial period.

NOTE

If you don’t see the orange glow, contact AERCO technical
support to ascertain the problem. If you DO see it, proceed to
the next step.

11. If the manometer reading is less than 3.0” w.c., increase the regulator setting by rotating the

adjustment screw clockwise (CW).

12. Repeat steps 8 through 11 until the gas pressure at the outlet of the RSI regulator reads

between 3.0” w.c. and 4.0” w.c. on the monometer.

13. Once the pressure reading is between 3.0” w.c. and 4.0” w.c., conduct at least three safe

RSI ignitions while observing the observation port. Assure the igniter lights immediately with
a strong orange flame after the Staged Ignition Solenoid Valve opens.

NOTE

Clear any Flame Loss During Ignition messages during the
tests by pressing The CLEAR key on control panel.

14. Close the external gas supply and RSI Staged Ignition Gas Valves. Disconnect the

manometer, tubing and barbed fitting from the 1/4” NPT port hole.

15. Bleed off any remaining pressure using the RSI bleed-off valve, then ensure this valve is

closed.

16. Replace the 1/4” plug in place of the barbed fitting.

17. OPEN the gas supply upstream of the unit.

Advertising