CHAPTER 3: CONTROL PANEL OPERATION

PR2: 04/22/13 Page 33 of 160


Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

3.5 SETUP MENU

The Setup Menu (Table 3-3) permits the operator to enter the unit password (159) which is
required to change the menu options. To prevent unauthorized use, the password will time-
out after 1 hour. Therefore, the correct password must be reentered when required. In
addition to permitting password entries, the Setup Menu is also used to enter date and time,
units of temperature measurements and entries required for external communication and
control of the unit via the RS-232 port. A view-only software version display is also provided
to indicate the current Control Box software version.

NOTE

The Outdoor Temp display item shown with an asterisk in
Table 3-2 will not be displayed unless the Outdoor Sensor
function has been enabled in the Configuration Menu
(Table 3-4).

Table 3-2: Operating Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Status Message

Active Setpoint

40°F

240°F

AIR Temp

-70°F

245°F

Outdoor Temp*

-70°F

130°F

Valve Position In

0%

100% Valve Position

Flame Strength

0%

100%

Run Cycles

0

999,999,999

Run Hours

0

999,999,999

Fault Log

0

19

0

Table 3-3: Setup Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Passsword

0

9999

0

Language

English

English

Time

12:00 am

11:59 pm

Date

01/01/00

12/31/99

Unit of Temp

Fahrenheit or Celsius

Fahrenheit

Comm Address

0

127

0

Baud Rate

2400, 4800, 9600, 19.2K

9600

Software

Ver 0.00

Ver 9.99