CHAPTER 6: SAFETY DEVICE TESTING

PR2: 04/22/13 Page 71 of 160


Benchmark 2.0LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0052_0E

GF-127

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

ACTUATOR

COVER

SCREW

SSOV

ACTUATOR

COVER

Figure 6-4: SSOV Actuator Cover Location

6.12 IGNITION SWITCH OPEN DURING IGNITION

The Ignition Switch (and the Purge Switch) is located on the Air/Fuel Valve. To check the
switch, proceed as follows:

1. Set the unit’s ON/OFF switch to the OFF position.

2. Place the unit in Manual Mode and set the valve position to 34%.

3. Remove the Air/Fuel Valve cover (Figure 6-5) by rotating the cover counterclockwise to

unlock and lift up to remove.

4. Remove one of the two wires (#169 or #170) from the Ignition Switch (Figure 6-6).

5. Initiate a unit start sequence.

6. The unit should begin it’s start sequence and then shut down and display IGN SWITCH

OPEN DURING IGNITION.

7. Replace the wire on the Ignition Switch and press the CLEAR button. The unit should

restart.

6.13 PURGE SWITCH OPEN DURING PURGE

The Purge Switch (and Ignition Switch) is located on the Air/Fuel Valve. To check the switch,
proceed as follows:

1. Set the unit’s ON/OFF switch to the OFF position. Place the unit in manual mode and set

the valve position to 34%.

2. Remove the Air/Fuel Valve cover by rotating the cover counterclockwise to unlock it and

then remove the cover (see Figure 6-5).

3. Remove one of the two wires (#171 or #172) from the Purge Switch (Figure 6-6).

4. Initiate a unit start sequence.

5. The unit should begin it’s start sequence, then shut down and display PRG SWITCH

OPEN DURING PURGE.

6. Replace the wire on the Purge Switch and depress the CLEAR button. The unit should

restart.