Table 6

Keyboard Directory

S T A T U S

QUICK TEST

KEYBOARD

DISPLAY

KEYBOARD ENTRY

DISPLAY

C O M M E N T

Factory/field test of

inputs

Leaving water

temperature

Entering water

temperature

Saturated suction temp

circuit A

Compressor suction
gas temp

A

Saturated suction temp
circuit B

Compressor suction
gas temp circuit B

Reset temperature

Loss of charge switch

circuit A

Loss of charge switch
circuit B

Oil pressure switch
circuit A

Oil pressure switch
Circuit B

Factory/field test of

outputs

Circuit A liquid line

solenoid test

Circuit B liquid line

solenoid test

Unloader A test

Unloader B test

A EXV open test

Circuit

Circuit B EXV open test

Circuit B EXV close test

Factory/field test of

compressors

Circuit A compressor 1
test

Circuit A compressor 2

test

Circuit B compressor 1

test

B compressor 2

test

C O M M E N T

Current alarm displays

Alarm 1

Alarm 2

Alarm 3

Current operating
mode displays

Mode 1

Capacity stages

Stage number

Current operating
set point

Leaving chilled water
set point

INPUTS

L W T X

EWT X

SSTA X

CGTA X

SSTB X

CGTB X

RST X

L C S A X

L C S B X

X

X

OUTPUTS

S L D A X

S L D B X

X

U N L B X

EXVAO X

EXVAC X

EXVBO X

EXVBC X

COMP

C A 1 X

C A 2 X

X

C B 2 X

X ALARMS

ALARM X

ALARM X

ALARM X

M O D E

MODE X

STAG ES

X STAGE

q

El

SET

If unit is in dual set point mode the set point currently in effect
is displayed.

Leaving water

temperature

System temperatures

Cooler leaving water

temp

Cooler entering water

temp

Saturated suction temp

circuit A

Compressor suction
gas temperature
circuit A

Superheat temp
circuit A

Saturated suction temp
circuit B

Compressor suction
gas temperature
circuit B

Superheat temp
circuit B

Reset temperature

Systems pressures

Circuit A loss of charge
switch

Circuit A oil pressure
switch

Circuit B loss of charge
switch

Circuit B oil pressure

switch

System analog values

Circuit A EXV valve
position

Circuit B EXV valve
position

TEMPS

L W T X

EWT X

SSTA X

CGTA X

S H A X

SSTB X

CGTB X

S H B X

RST X

PRESS

LCSA X

X

LCSB X

X

During test of compressors, each compressor will start and
run for 10 seconds. Compressor servicevalves and the liquid
line valve must be open. Energize compressor crankcase
heaters for 24 hours prior to performing compressor tests.

A N A L O G

EXVA X

EXVB X

END TEST

Leave quick test

7