Carrier HS070-160 User Manual

Page 9

Advertising
background image

Table 7

Display Codes

OPERATING MODES

Display

Description

Comp Al Al

Failure

Failure

C o m p

Failure

Comp

B 2

Failure

Loss of charge circuit A
Loss of charge circuit B

Low cooler flow

Low oil pressure circuit A
low oil pressure circuit B

Freeze protection

High suction superheat circuit A
High suction superheat circuit

B

Low suction suoerheat circuit A

Low suction superheat circuit B

Leaving water thermistor failure

Entering water thermistor failure

Cooler thermistor failure circuit A
Cooler thermostor failure circuit B
Comp thermistor failure circuit A
Comp thermistor failure circuit B

Reset thermistor failure

ALARMS

Action

Taken

Control

Circuit A shut off
Comp shut off
Circuit B shut off
Comp shut off

Circuit A shut off

Circuit B shut off

Unit shut off

Circuit A shut off
Circuit B shut off

Unit shut off

Circuit A shut off
Circuit B shut off

Circuit A shut off
Circuit

shut off

Unit shut off
Use default value
Circuit A shut off
Circuit B shut off
Circuit A shut off
Circuit B shut off
Stop reset

Reset

Method

M a n u a l
M a n u a l
M a n u a l
M a n u a l

M a n u a l
M a n u a l

M a n u a l

M a n u a l
m a n u a l

Auto.

M a n u a l
M a n u a l

M a n u a l
M a n u a l

Auto.
Auto.
Auto.
Auto.
Auto.
Auto.
Auto.

Probable Cause

High pressure switch trip or high discharge gas temp
switch trip, on when it is not supposed to be on. Wiring
error between electronic control and compressor relay.

Low refrigerant charge, or loss of charge pressure switch
failure.

No cooler flow or reverse cooler flow

Oil pump failure or low oil level, or switch failure.

Low cooler flow

Low charge or EXV failure, or plugged filter drier.

EXV failure

cooler thermistor error.

Thermistor failure, or wiring error, or thermistor not
connected to input terminals.

NOTES:
1. Freeze protection trips at 35 F (1.7 C) for water and 6 degrees F (3.3 degrees C) below set point

for brine units. Resets at 6 degrees above set point.

2. All auto. reset failures that cause the unit to stop will restart the

when the error has been

corrected.

3. All manual reset errors must be reset by moving the control switch to STANDBY then to RUN.
4. Valid resistance range for thermistors is 363,000 ohms to 216 ohms.