-­‐Industrial  Line-­‐  

TYPICAL  SPECIFICATIONS  

 

Supply  an  ICE  (US),  Inc.  direct  fired  make-­‐up  unit  designed  for  (indoor)  (outdoor)  installation.  The  
capacity  and  configuration  shall  be  as  detailed  on  the  drawings.  The  unit  shall  be  CGA  and  ETL  
certified  and  listed  to  be  in  compliance  with  the  current  ANSI  Z83.18  standard.  
 
The  line  burner,  gas  train  and  controls  are  to  be  in  accordance  with  (ANSI)  (FM)  (IRI)  (FM  and  IRI)  
requirements.  Both  burner  and  blower  shall  be  compensated  for  altitude  of    operation.  
 
The  unit  is  to  be  completely  factory  test  fired  to  verify  proper  operation.  The  unit  capacity  is  to  be  
validated  with  an  instantaneous  flow  meter.  A  complete  electrical  circuit  analysis  is  to  be  conducted  
and  all  systems  operated  and  measured.  A  combustion  analyzer  is  to  be  employed  while  unit  is  
operating  at  full  capacity  to  verify  combustion  emissions.  Burner  combustion  must  be  clean  and  
odorless  and  no  aliphatic  aldahydes  are  to  be  detectable.  Combustion  efficiency  must  limit  the  
products  of  combustion  to  a  maximum  of  5  ppm  carbon  monoxide  and  0.5  ppm  nitrogen  dioxide.  
 

 
UNIT  CASING  

Unit  construction  is  to  be  of  industrial  quality  heavy  gauge  bonderized  steel.  The  unit  design  shall  
incorporate  a  full  base  pan  supported  by  an  integral  welded  channel  iron  base.  Bases  are  to  be  of  
industrial   welded   structural   iron   integrity,   formed   sheet   metal   bases   are   unacceptable.   All  
structural  iron  base  supports  are  to  be  treated  with  an  industrial  epoxy  primer  enriched  with  a  rust  
inhibitor.  
 
To  ensure  the  casings  are  airtight  and  weatherproof,  all  panels  are  to  be  caulked  during  assembly.  
All  casings  are  to  be  hand  fitted  and  secured  with  gasketed  self-­‐tapping  tek  screws.  Roof  casing  are  
to  feature  three-­‐break  standing  seam  panel  design.  Roof  casings  are  to  be  sloped  on  outdoor  units  
to  prevent  standing  water.  Sloped  roofs  are  to  be  ¼  in.  per  foot  and  feature  full  drain  troughs.  
 
Entire  unit  casing  and  accessories  are  to  be  insulated  with  fiberglass  insulation  with  hard  neoprene  
facing.  (1  or  2  in.  thick  1-­‐1/2#  or  2#  density)  insulation  is  to  be  secured  with  industrial  glue  and  
welded   pin   spots.   Insulation   is   to   be   certified   to   fire   and   flamespread   ratings   as   outlined   by   the  
ANSI  code.  The  entire  floor  of  the  unit  is  to  feature  a  steel  liner  sandwiching  the  insulation.  
 
Units  are  to  be  equipped  with  access  doors  to  all  serviceable  components.  Access  doors  are  to  have  
full-­‐length  stainless  steel  piano  hinges.  All  access  doors  are  to  be  equipped  with  an  insulation  liner,  
positive   seal   latches   and   gasketing   .   Access   doors   are   to   open   outward   on   negative   pressure  
sections   and   inward   on   positive   pressure   sections.   Access   doors   to   feature   6   in.   handles   with  
locking  roller  mechanism  for  ease  of  latching.  All  outdoor  unit  access  doors  are  to  be  equipped  with  
drain  troughs.  
 
Units  are  to  be  finished  with  an  industrial  grade  chain  stop  alkyd  enamel  paint.  The  medium  grey  
finish  coat  is  to  be  a  mimum  of  3  mils  thick  and  provide  100%  coverage.  