Interlogix ESL DH Series User Manual

Interlogix Safety

Advertising
background image

1

Floor-Mount Electromagnetic Door
Holder Installation Instructions

Description

The Floor-Mount Electromagnetic Door Holder is designed

for use in fire door applications. The door holder is

controlled by a UL Listed fire alarm control panel.

Wiring Instructions

Installing the Electromagnetic

ESL

Selecting a Location for the Conduit

When installing the door holder, the conduit wiring is pulled

through the center of the mounting gasket and base plate.

To allow enough space for the door holder assembly, make

sure there is a 6-inch diameter clearance around the conduit

location.

All wiring must conform to the National Electric Code

(NEC) and/or local codes having jurisdiction.

Important: When you connect the wiring for the single-

coil or double-coil 24/120 door holder, attach the green wire

to the earth ground.

Assembly

Step 1:

Using the gasket as a template, mark the four outer corner

drill hole locations on the floor. Check the alignment of the

gasket to ensure the door magnet(s) will be as flush as

possible with the door(s).

Step 2:

Drill holes 3/8 inch diameter by 1 to 1

1/8 inch (preferably 1 1/16 inch)

deep in floor. Insert the cement

anchors in the drill holes. Hammer

each anchor down until it is flush

with the floor, and then expand the

anchor with the provided setting tool.

Step 3:

Line up the gasket and base plate with the holes, pull the

conduit wiring through the center hole, and place the gasket

and base plate on the floor. Make sure the base plate has

the extruded-thread side up.

Step 4:

Secure the gasket and base plate to the floor with the four

retaining screws.

Step 5:

Connect the conduit wiring to the

electromagnetic assembly. See

Wiring Instructions.

Step 6:

Line up the two screw holes on the

electromagnetic assembly with the

two raised screw holes on the base

plate, and then place the assembly

over the base plate and onto the

gasket. Make sure each magnet is

facing a door (one or two

depending on the model).

Step 7:

Secure the electromagnetic

assembly to the base plate using

the two retaining screws.