LAARS Rheos RHCV - Install and Operating Manual User Manual

Page 19

Advertising
background image

Rheos Boiler and Water Heater

Page 19

Increase the head loss requirement by 20%.

IMPORTANT NOTES: Different glycol products

may provide varying degrees of protection. Glycol

products must be maintained properly in a heating

system, or they may become ineffective. Consult the

glycol specifications, or the glycol manufacturer, for

information about specific products, maintenance

of solutions, and set up according to your particular

conditions.

SECTION 4B.

Water Connections —

Rheos Water Heater

4B.1 Water System Piping —

Water Heater

Hot water piping should be supported by suitable

hangers or floor stands. Do not support piping with

this appliance. Due to expansion and contraction of

copper pipe, consideration should be given to the type

of hangers used. Rigid hangers may transmit noise

through the system resulting from the piping sliding in

the hangers. It is recommended that padding be used

when rigid hangers are installed.

The Rheos can be used with several different

types of readily available storage tanks. A pump draws

water from the storage tank and pumps the water

through the heater and back into the tank. Pump-

mounted units have a circulating pump built into the

water heater.

Pipe the outlet from the heater’s relief valve

such that any discharge from the relief valve will be

conducted to a suitable place for disposal when relief

occurs. Do not reduce line size or install any valves in

this line. The line must be installed to allow complete

drainage of both the valve and the line.

Suggested piping diagrams are shown in Figures

9, 10, 11 and 12. These diagrams are meant only as a

guide. Components required by local codes must be

properly installed.

The minimum inlet water temperature for the

Rheos is 130°F (54°C) to avoid condensing on the

copper coils.

4B.2 Hot Water Supply Piping —

Water Heater

Follow the tank manufacturer’s guidelines for

completion of the hot water system connections.

feet (9.1m) of full-sized piping and a normal number

of fittings.

Table 8 specifies water flow rates for boilers,

which will enable the user to size a pump. The

headloss shown is for the heater only, and the user

will need to add the headloss of the system piping to

properly size the pump.

The minimum inlet water temperature for the

Rheos is 130°F (54°C) to avoid condensing on the

copper coils.

4A.4 Freeze Protection – Boiler

Proper precautions for freeze protection are

recommended for boiler installations in areas where

the danger of freezing exists.

Power outage, interruption of gas supply, failure

of system components, activation of safety devices,

etc., may prevent a boiler from firing. Any time a

boiler is subjected to freezing conditions, and the

boiler is not able to fire, and/or the water is not able

to circulate, there is a risk of freezing in the boiler

or in the pipes in the system. When water freezes,

it expands. This can result in bursting of pipes in the

system, or damage to the boiler, which could result in

leaking or flooding conditions.

Do not use automotive anti-freeze. Maintaining

a mixture of minimum 50% water and maximum

50% properly inhibited HVAC glycol, which contains

an antifoamant, is the preferred method of freeze

protection for Rheos boilers. Percentage of glycol

used in the Rheos boiler must not exceed 50%.

Typically, this mixture will serve as burst protection

for temperatures down to approximately –35°F (-

30°C). To get the desired temperature rise across the

boiler when this mixture is used, increase the water

flow by 15% above the original recommendation.

Connector

Module

Dial

Setpoint Adjustment

Differential

Adjustment

Energized

Relay
LED Indicator

Relay

VDC

COM

24V

SEN

Jumper Block

Position

Heating
Cooling

Note: Jumper must

be in “Heating” mode,

or Rheos will not

operate properly.

Figure 13. Temperature Control.

Advertising
This manual is related to the following products: