Warning, Danger – Dunkirk Excelsior EXB Series User Manual

Page 53

Advertising
background image

53

18.1 Annually

Recommend qualified Service Agency check at lease once a

year:

• Flue passages,
• Combustion chamber area (target wall, fire door

insulation)

• Burner adjustment,
• Operation of the controls,
• Boiler seals (fire door gasket or silicone seal, cast iron

sectional seals, flue collector)

Before start of each heating season (or system has been

shut down for extended period of time)

• Recheck whole system for water, oil, and vent piping

leaks.

• Replace or patch any leaks or seals that are faulty
• Inspect flue ways at least once a year- Preferably at

start of heating season.

• Inside of combustion chamber.
• Clean vent system and boiler flue ways if soot or scale

has accumulated. When cleaning, take precaution

to avoid damage to burner swing door insulation. If

damaged, or if there is evidence of previous damage,

burner swing door insulation must be replaced

immediately.

• Oil Burner and controls.

18.2 Vent Pipe

Visually inspect entire venting system once a month for any

signs of leakage, deterioration, or soot build up.
If vent pipe shows any signs of leaking or deterioration,

replace it immediately.
If it shows any signs of soot build up, clean vent pipe and

have burner settings and combustion checked by qualified

service agency.

18.3 Relief Valve

• Test relief valve for proper operation. Refer to valve

manufacturer’s instructions packaged with relief valve.

18.4 Conventional Expansion Tank

See “Equipment And Accessories” section.

18.5 Diaphragm Expansion Tank

See “21 - Equipment And Accessories” on page 59.

18.6 WATER SYSTEM
Drain system completely if system is to remain out of

service during freezing weather. Water left in system will

freeze and crack pipes and/or boiler.

18.7 Oil Burner Maintenance

Beckett AFG, perform following preventative maintenance

annually, preferably prior to heating season.

• Fuel Filter Replace to prevent contaminated fuel from

reaching nozzle. Partially blocked fuel filter can cause

premature failure of fuel pump.

• Fuel Pump Unit Replace pump screen and clean pump

unit to maintain fuel delivery to nozzle.

• Ignition Electrodes Clean and adjust as per

manufacturer’s recommendations, so as to maintain

reliable ignition of oil.

• Nozzle Replace so as to maintain safe and reliable

combustion efficiency. Always replace with exact nozzle

as required in charts. See “17 - Oil Burner, Nozzle, &

Air Settings” on page 46.

• Fan and Blower Housing Keep clean, free of dirt, lint

and oil to maintain proper amount of air fuel requires to

burn.

• Check burner settings and adjust as needed.

NOTE: If any component parts must be replaced, always

use parts recommended by burner manufacturer.

18.8 Maintenance Of Optional Low Water Cut Off

WARNING

Burn and scald hazard. Verify boiler is at zero

pressure before removing relief valve or control well.

Open safety valve to relieve all internal pressure

prior to proceeding.

!

Remove control well from top of rear boiler section every

five years and clean any scale or sediment deposits from all

parts exposed to boiler water.

18 - MAINTENANCE

DANGER

Before servicing, turn off electrical power to boiler

at service switch. Turn off fuel supply to burner

Failure to comply will result in death or serious

injury.

!

NOTICE

Perform regular service and maintenance by

qualified service agency at least once every 12

months to assure safe, trouble free operation

and maximum efficiency.

NOTICE

Verify proper operation after servicing.

Advertising