IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
CAUTION – To prevent electrical shock, do not mate unit connector until full installation is complete and A.C.
power is supplied to the unit.
2.
CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-
necting the unit connector.
3.
CAUTION – This is a sealed unit. Components are not replaceable. Replace the entire unit when necessary.
4.
CAUTION – Installation and servicing should be performed by qualified personnel only. Do not open this
unit.
5.
DO NOT USE OUTDOORS. The ILB-3020 is for use with grounded, UL Listed, indoor fixtures. Not for use in
heated air outlets or hazardous locations.
6. The
ILB-3020 requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused
A.C. lead.
7. The
ILB-3020 and A.C. ballast must be on the same branch circuit.
8. Do not mount near gas or electric heaters.
9. The
ILB-3020 should be mounted in locations and at heights where it will not readily be subjected to tamper-
ing by unauthorized personnel.
10. The
ILB-3020 will supply up to 24 watts for 90 minutes.
11. The
ILB-3020 must be supplied a minimum of 19.2VDC @ 2500mAh (16 C cells of 2.5 Ahs).
12. The
ILB-3020 is compatible with all A.C. magnetic and electronic ballasts including multiple lamp ballasts with
one lamp operating in the emergency mode.
13. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
14. Do not use this equipment for other than intended use.
15. Install in accordance with the National Electrical Code and local regulations.
16. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation.
17. Do not disconnect DC power with AC power supplied. Always disconnect AC power first.
SAVE THESE INSTRUCTIONS
ILB-3020
LED
EMERGENCY
LIGHTING EQUIPMENT
INSTRUCTION MANUAL
THIS UNIT CONTAINS A
RECHARGEABLE NICKEL-
CADMIUM BATTERY. PLEASE
RECYCLE OR DISPOSE OF
PROPERLY.
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 • FAX (520) 741-2837
www.iotaengineering.com