Figure 33 - Connecting Flexible Gas Line

to Millivolt Valve

Flexible Gas Line
Do NOT Kink

Equipment
Shutoff Valve

To Gas Supply
(Natural)

To External
Regulator
(Propane/LP)

Control Valve

FIREPLACE

INSTALLATION

Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect fireplace and its individual

equipment shutoff valve from gas supply
piping system. Pressures in excess of 1/2
psig (3.5 kPa) will damage fireplace gas
regulator.

2. Cap off open end of gas pipe where equip-

ment shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve
for propane/LP gas fireplace or opening
main gas valve located on or near gas
meter for natural gas fireplace or using
compressed air.

4. Check all joints of gas supply piping sys-

tem. Apply noncorrosive leak detection

fluid to all joints. Bubbles forming show a
leak. Correct all leaks at once.

5. Reconnect fireplace and equipment

shutoff valve to gas supply. Check recon-
nected fittings for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig-

ure 34).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve
for propane/LP gas fireplace or opening
main gas valve located on or near gas
meter for natural gas fireplace or using
compressed air.

3. Check all joints from propane/LP supply

tank or gas meter to equipment shutoff
valve (see Figure 35 or Figure 36). Ap-
ply noncorrosive leak detection fluid to
all joints. Bubbles forming show a leak.
Correct all leaks at once.

Figure 34 - Equipment Shutoff Valve

Open

Closed

Equipment
Shutoff Valve

Figure 35 - Checking Gas Joints for

Propane/LP Gas Fireplace

Propane/LP
Supply Tank

Gas Valve

Equipment Shutoff Valve

Figure 36 - Checking Gas Joints for

Natural Gas Fireplace

Gas
Meter

Gas Valve

Equipment
Shutoff Valve