Installation, Hazardous location considerations, Prevent electrostatic discharge – Spectrum Controls 1762sc-IF8U User Manual

Page 4

Advertising
background image

MicroLogix™ Universal Analog Input Module

4

Publication 0100151-02 Rev. B

Installation

1762 I/O is suitable for use in an industrial environment when installed in
accordance with these instructions. Specifically, this equipment is
intended for use in clean, dry environments (Pollution degree 2

(1)

) and to

circuits not exceeding Over Voltage Category II

(2)

(IEC 60664-1).

(3)

Prevent Electrostatic Discharge


Electrostatic discharge can damage integrated
circuits or semiconductors if you touch bus connector
pins. Follow these guidelines when you handle the
module:

 Touch a grounded object to discharge static

potential.

 Wear an approved wrist-strap grounding

device.

 Do not touch the bus connector or connector

pins.

 Do not touch circuit components inside the

module.

 If available, use a static-safe work station.

 When not in use, keep the module in its

static-shield box.







(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution
occurs except that occasionally a temporary conductivity caused by condensation shall be
expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At
this level transient voltages are controlled and do not exceed the impulse voltage capability
of the product’s insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical
Commission (IEC) designations.

MicroLogix™ Universal Analog Input Module

21

Publication 0100151-02 Rev. B

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C,
D or non-hazardous locations only. The following WARNING statement
applies to use in hazardous locations.

EXPLOSION HAZARD

 Substitution of components may impair

suitability for Class I, Division 2.

 Do not replace components or disconnect

equipment or change the current switch
selection switch position unless power has
been switched off.

 Do not disconnect equipment unless power

has been removed or the area is known to
be non-hazardous.

 This product must be installed in an

enclosure.

 In Class I, Division 2 applications, the bus

connector must be fully seated and the
bus connector cover must be snapped in
place.

 In Class I, Division 2 applications, all

modules must be mounted in direct
contact with each other as shown on page
6. If DIN rail mounting is used, an end
stop must be installed ahead of the
controller and after the last 1762 I/O
module.

 All wiring must comply with N.E.C. article

501-4(b).