Power requirements, Input specifications, Panel mounting – Spectrum Controls 1762sc-IF8U User Manual

Page 7

Advertising
background image

MicroLogix™ Universal Analog Input Module

18

Publication 0100151-02 Rev. B

Specification

Value

Vendor I.D.

58

Product Type

10

Product Code

20

Agency Certification

C-UL listed (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives

Hazardous Environment
Class

Class I, Division 2, Hazardous Location, Groups A, B,
C, D
(ISA 12.12.01, C-UL under CSA C22.2 No. 213)
Operating Temperature Code T5

Radiated and
Conducted Emissions

EN55011

Electrical /EMC:

The module has passed testing at the following levels:

ESD Immunity
(IEC61000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated Immunity
(IEC61000-4-3)

10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed
carrier

Fast Transient Burst
(IEC61000-4-4)

2 kV, 5 kHz

Surge Immunity
(IEC61000-4-5)

1 kV galvanic gun

Conducted Immunity
(IEC61000-4-6)

10V, 0.15 to 80 MHz

4

Input Specifications

Specification

Value

Number of Inputs

8 Current/Voltage or 4 Resistance

A/D Converter Type

Delta Sigma

Common Mode Rejection

100 dB for 4 Hz & 17 Hz Filters

Non-linearity (in percent
full scale)

±0.1%

Input Impedance

Current Terminal: 249Ω

Current Input Protection

±42 mA

Voltage Input Protection

±28 V

5

                                                            

4

 

Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated

Immunity frequency range is 30 MHz to 2700 MHz.

 

5

 The maximum allowable voltage difference between any two input pins is 

28V. 

MicroLogix™ Universal Analog Input Module

7

Publication 0100151-02 Rev. B


For environments with extreme vibration and
shock concerns, use the panel mounting
method described below, instead of DIN rail
mounting.

Panel Mounting

Use the dimensional template shown below to mount the module. The
preferred mounting method is to use two M4 or #8 panhead screws per
module. M3.5 or #6 panhead screws may also be used, but a washer
may be needed to ensure a good mechanical contact. Mounting screws
are required on every module.

Power Requirements

The maximum number of IF8U modules that can be installed in a system
depends on the maximum bus current draw of the module and the
maximum bus current provided by the PLC. The IF8U module has the
following power requirements.

5 VDC

24 VDC

175 mA 21 mA