CIRCUTOR computer SMART III-Fast Series User Manual
Page 11
Advertising
![background image](/files/767856/content/doc011.png)
CORRECT
INCORRECT
~
P1
P2
S1
S2
TC
LOAD
CAPACITORS
Thecurrenttransformers(CT)must
measure the combined current of
thecapacitorsplustheloads
If it does not work, make sure
that the CTs are not short-
circuited�
~
LOAD
CAPACITORS
P1
P2
S1
S2
TC
I f t h e C Ts a r e c o n n e c t e d
i n t h i s p o s i t i o n , N O N E O F
THE CAPACITORS WILL BE
CONNECTED,evenifthereare
inductiveloads�
The unit does not compensate�
~
LOAD
CAPACITORS
P1
P2
S1
S2
TC
IftheCTsareconnectedinthis
positionALLTHECAPACITORS
WILLBECONNECTED,butthey
willnotbedisconnectediftheload
drops�
Risk of over-compensation in
the grid with no load�
Figure 1: Location of the current transformers
11