User Instructions - Logix® 500+ Series Digital Positioners FCD LGENIM0105-10 11/13
flowserve.com
38
NOTE: Once the Multi-Function Card (MFC) type has
been configured, the type selection will still remain after a
factory reset.
CAUTION: Performing a factory reset may result in the
inability to operate the valve until reconfigured properly.
Notify proper personnel that the valve may stroke, and make
sure the valve is properly isolated.
10.3.14 Card 1 (or Card 2)
Two slots are available for auxiliary cards. The Multi-
Function Card (MFC) can be configured for analog output
(AO), Discrete Input (DI) and Discrete Output (DO).
No Card – This is displayed when no card is present in the
slot.
Multi-Function Card – This is displayed when a Multi-
Function Card is present in the slot. Configuration options
follow. See section 13 MULTI-FUNCTION CARD for more
information.
Not Configured – The MFC is not configured for any function
by default. The configuration must be set by using the
following functions.
Set as AO Card – Use this feature to set the MFC as an
analog output card.
Set as DO Card – Use this feature to set the MFC as a
discrete output card.
Set as DI Card – Use this feature to set the MFC as a
discrete input card.
Config/Cal – Use this feature to further configure the FMC.
The menu items below this level will change according to the
MFC configuration type selected.
If Not Configured
No Configuration Allowed – Because the card type has not
been selected, no configuration options are available.
If Set As AO Card
Set 0% - Set the current (mA) that will correspond to the
0% (closed) valve position.
Set 100% - Set the current (mA) that will correspond to the
100% (open) valve position.
NOTE: The AO calibration values are required to match
the “Signal At Closed” configuration switch on the positioner.
For example, if the switch is set to 4 mA, the “Set 0%” current
must be less than the “Set 100%” current.
If Set As DO Card
Use DTM – The DO is highly configurable. Use the
ValveSight DTM to set the function of the DO.
If Set As DI Card
Set to No Action – Use this option if only an
acknowledgement of the DI state is desired.
Set to Trigger PST – Use this option to initiate a partial
stroke test when the DI state goes high.
Set to Command Override - Use this option to override the
analog or digital command input to move the valve to a set
position as long as the DI state remains high.
Set Command Point – Use this feature to set the override
position. The position is a final command (not
characterized). Tight Shutoff settings and Soft Limits will
still apply.
10.3.15 Language
The display menu is available in several languages.
To navigate directly to the language menu, select the
following sequence of buttons:
▲Up , ▲Up, ►QUICK-CAL /
ACCEPT.
►Card 1 (or Card 2)
►No Card
►Card 1 (or Card 2)
►Multi-Function Card
►Not Configured
►Set as AO Card
►Set as DO Card
►Set as DI Card
►Config/Cal
►
If Not Configured – “No Configuration Allowed”
►
If AO
►
Set 0%
►
Set 100%
►
If DO – “Use DTM”
►
If DI
►
Set to No Action
►
Set to Trigger PST
►
Set to Command Override
►
Set Command Point
► Language
►English
►German
►French
►Spanish
►Portuguese
►Russian
►Turkish
►Italian