4 – diagnostics, calibration, and troubleshooting, Def dispenser problems, Def dispenser problems -1 – Gasboy DEF Atlas User Manual

Page 13: Important information

Advertising
background image

MDE-5044A Atlas® DEF Operation, Diagnostics, and Recommended Spare Parts Manual · April 2014

Page 4-1

Diagnostics, Calibration, and Troubleshooting

DEF Dispenser Problems

4 – Diagnostics, Calibration, and Troubleshooting

DEF Dispenser Problems

Following section is provided to guide you through possible DEF dispenser problems. For
more information, refer to MDE-4331 Atlas Fuel Systems Installation Manual, MDE-4334
Commercial and Retail Series Atlas Start-up/Service Manual,
and FE-356 Field Wiring
Diagram Atlas Retail, Commercial, E-85, and DEF Dispensers with Electronic and
Mechanical Displays
.

Before beginning any troubleshooting session, it is advisable to follow these steps:

• Perform a visual inspection of the dispenser to ensure that it is installed according to

MDE-4331 Atlas Fuel Systems Installation Manual.

• Ensure that all cables and switch settings are connected and set properly according to

MDE-4331 Atlas Fuel Systems Installation Manual and MDE-4334 Commercial and
Retail Series Atlas Start-up/Service Manual
.

• Measure the DC power supply output voltages to ensure that they are proper operating

tolerances.

• Observe all the LEDs on all the Printed Circuit Boards (PCBs) to ensure that proper signal

is present.

• Observe the customer display and verify if any error messages are present.
• Verify if this is a new start-up or an existing unit, and for how long has it been in

operation.

Note: Before beginning any troubleshooting session, it is helpful to use the

“Flow Chart”

on

page 4-3

and the

“Atlas DEF Block Diagram”

on

page 4-4

.

Following table shows possible symptoms, causes, and corrective actions:

Problem 1: Entire unit is down/dead.

Symptoms

• No customer display.
• Display is blank.
• Unable to reset unit.
• Unable to dispense product.
• No LEDs light on any PCBs.

Possible Causes

• No 115 VAC feed to dispenser.
• Dispenser’s circuit breaker is off.
• Blown system fuse.
• Loose or disconnected AC wiring in Junction Box (J-box).

Corrective Action

• Turn on AC breaker for the dispenser, if off.
• Ensure 115 VAC at all power supplies input.
• Check system fuse if AC is not present in the power supply.
• Check and measure the AC voltage in the J-box, if all of the above fails.

An intermitting or bad 9800 power supply can cause the symptoms mentioned in

“Problem 1: Entire unit is down/dead.”

, always with the exception of AC power (+5 VDC)

present in the unit.