5-2.4. Communication Troubleshooting

The troubleshooting procedure for problems related to communication to peripherals and
consequent corrective actions are described in Table 5-4.

Table 5-4. Communication Troubleshooting

Fault

Probable Cause

Checks

Corrective Action

No communication between FHO and SO controller

No connection to
the station from
FHO Stations
screen

Cabling issue

Visually inspect the
network cable to
LAN2

1. Verify that LAN2 Port LED

is blinking

2. Unplug the cable and plug it

back in

3. Replace LAN cable, if

necessary

4. If the cable is in good

condition, contact the IT
department to confirm that
the switch/router connected
to the LAN cable is properly
set

5. Check the Controller

network settings (IP
addresses, mask, gateway,
etc.)

No communication to the pumps (8-port CommVerter)

"Warning" signs
displayed for all
pumps on the
SiteOmat Status
screen

Incorrect 8-port
CommVerter setup

Check the physical
connection of the 8-
port CommVerter to
the local network (5-
port switch activity)

1. If no activity on the LAN

port connected to the 8-port
CommVerter, replace the
short Ethernet cable or/and
change the LAN port to
confirm normal operation