Specifications, Overview, Environmental – Geist Upgradeable PDU User Manual
Page 4: Temperature, Humidity, Elevation, Electrical, Part i specifications, 1specifications, 1 overview
Upgradeable PDU Instruction Manual
4
© 2015 Geist
GM1157 - GU PDU Instruction Manual
1
Specifications
1.1
Overview
The new Geist Upgradeable PDU gives data-center managers the flexibility to install
the intelligence they require today, with the option to upgrade technology as needs
evolve. From basic power to power monitoring, the Geist Upgradeable product line
adapts to your business well into the future.
To establish this extraordinary upgrade path, our engineers took Geist's robust PDU
design and incorporated an Interchangeable Monitoring Device (IMD). Geist's rugged
PDUs last for many years, and with the new IMD design, users will be able to upgrade
their PDUs to newer monitoring technologies in the future without having to replace the
entire PDU. The hot-swappable IMD can be changed out in a few simple steps,
without interrupting power to critical servers.
1.2
Environmental
1.2.1 Temperature
Operating
10°C (50°F)
min
45°C (122°F) max (full nameplate
current load)
60°C (140°F) max (50% of max
nameplate and receptacle current
rating)
Storage
-25°C (-13°F)
min
65°C (149°F) max
1.2.2 Humidity
Operating
5% min
95% max (non-condensing)
Storage
5% min
95% max (non-condensing)
1.2.3 Elevation
Operating
0 m (0 ft) min
3050 m (10000 ft) max
Storage
0 m (0 ft) min
15240 m (50000 ft) max
1.3
Electrical
See nameplate for unit ratings.