9 inspection of fan motor, 10 inspection of compressor motor, Inspection of fan motor – MovinCool Office Pro 63 Service Manual User Manual
Page 61: Inspection of compressor motor
Repair Section
61
8.9 Inspection of Fan Motor
(1) Condenser fan motor
• Measure resistance across the terminals of the
fan motor. (All terminals must be disconnected
from the unit.)
• Between terminals (at 77 °F (25 °C))
- J6-CF11 Approx. 3.5 ohm
- J6-CF12 Approx. 6.0 ohm
- CF11-CF12 Approx. 9.1 ohm
• If the measured resistance is not equal to these
standard values, replace the fan motor.
(2) Evaporator fan motor
• Measure resistance across the terminals of the
fan motor. (All terminals must be disconnected
from the unit.)
• Between terminals (at 77 °F (25 °C))
- J8-CF21 Approx. 7.6 ohm
- J8-CF22 Approx. 10.4 ohm
- CF21-CF22 Approx. 17.7 ohm
• If the measured resistance is not equal to these
standard values, replace the fan motor.
8.10 Inspection of Compressor Motor
• Measure resistance across the terminals of the
compressor motor. (All terminals must be
disconnected from the unit.)
• Between terminals (at 77 °F (25 °C))
- R-C Approx. 0.4 ohm
- C-S Approx. 0.6 ohm
- S-R Approx. 0.9 ohm
• If the measured resistance is not equal to these
standard values, replace the compressor. The
overload relay is internal to the compressor.
I001775
Condenser Fan Motor
Ground (Green/Yellow)
J5 Low (Red)
CF12 (Brown/White)
CF11 (White or Orange)
J6 High (Black)
I001774
Evaporator Fan Motor
Ground (Green/Yellow)
J7 Low (Red)
CF22 (Brown/White)
CF21 (White)
J8 High (Black)
I001945
R
T3
S
T2
C
T1