Yaskawa 1000 Series Drive Option - Profibus-DP Technical Manual User Manual
Page 31
8 Parameter Process Data Object Formats
YASKAWA ELECTRIC
SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual
31
MaxTsdr_9.6
60
60 Tbit = 6.25 msec
MaxTsdr_19.2
60
60 Tbit = 3.125 msec
MaxTsdr_45.45
60
60 Tbit = 1.32 msec
MaxTsdr_93.75
60
60 Tbit = 640 usec
MaxTsdr_187.5
60
60 Tbit = 320 usec
MaxTsdr_500
100
100 Tbit = 200 usec
MaxTsdr_1.5M
150
150 Tbit = 100 usec
MaxTsdr_3M
250
250 Tbit = 83 usec
MaxTsdr_6M
450
450 Tbit = 75 usec
MaxTsdr_12M
800
800 Tbit = 67 usec
Min_Slave_Interval
5
Minimum slave interval=0.5 ms
Freeze_Mode_supp 1
Freeze
mode not supported
Sync_Mode_supp 1
Sync
mode not supported
Fail_Safe
1
Fail safe supported
DPV1_Slave
1
DPV1_Data_Types 1
C1_Read_Write_supp
0
C2_Read_Write_supp
1
C2_Max_Data_Len
240
C2_Response_Timeout
100
C2_Read_Write_required
0
C2_Max_Count_Channels
1
Max_Initiate_PDU_Length
52
Modular_Station
1
Modular station.
Max_Module
1
Maximum # of modules: 1
Max_Input_Len
32
Maximum # of input bytes
Max_Output_Len
32
Maximum # of output bytes
Max_Data_Len
64
Maximum # of data bytes
Max_User_Prm_Data_Len 4
Ext_User_Prm_Data_Const(0) 0x40,0x01,0x00,0x01
Ext_User_Prm_Data_Ref(0)
1
Ext_User_Prm_Data_Ref(0)
2
Max_Diag_Data_Len
11
Maximum diagnostic length
Unit_Diag_Bit(0024)
“Undervoltage Condition”
Unit_Diag_Bit(0025)
“Inverter Communications Error”
Unit_Diag_Bit(0026)
“PNU915: Illegal PNU configured”
Unit_Diag_Bit(0027)
“PNU916: Illegal PNU configured”
Parameter
Setting Value
Note