6 Related Drive Parameters

34

YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual

F7-12

(3E0)

<7>

Gateway Address 4

Sets the static/fixed Gateway address.
Parameter F7-12 sets the fourth most significant octet.

Default: 1
Range: 0 to
255

F7-13

(3F1)

Address Mode at
Startup

Selects how the option address is set.
0: Static

<6>

1: BOOTP
2: DHCP

Default: 2
Range: 0 to 2

F7-14

(3F2)

Duplex Mode
Selection

Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate
2: Full duplex forced

Default: 1
Range: 0 to 2

F7-15

(3F3)

<8>

Communication Speed
Selection

Sets the communication speed
10: 10 Mbps
100: 100 Mbps

Default: 10
Range: 10, 100

F7-17

(3F5)

EtherNet/IP Speed
Scaling Factor

Sets the scaling factor for the speed monitor in EtherNet/IP
Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-18

(3F6)

EtherNet/IP Current
Scaling Factor

Sets the scaling factor for the output current monitor in
EtherNet/IP Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-19

(3F7)

EtherNet/IP Torque
Scaling Factor

Sets the scaling factor for the torque monitor in EtherNet/IP
Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-20

(3F8)

EtherNet/IP Power
Scaling Factor

Sets the scaling factor for the power monitor in EtherNet/IP
Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-21

(3F9)

EtherNet/IP Voltage
Scaling Factor

Sets the scaling factor for the voltage monitor in EtherNet/IP
Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-22
(3FA)

EtherNet/IP Time
Scaling

Sets the scaling factor for the time monitor in EtherNet/IP
Class ID 2AH Object.

Default: 0
Min.: -15
Max.: 15

F7-23 to

F7-32

(3FB to 404)

Dynamic Output
Assembly Parameters

Parameters used in Output Assembly 116. Each parameter
contains a MEMOBUS/Modbus address. The value received
for Output Assembly 116 will be written to this
corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the
value received for Output Assembly 116 will not be written
to any MEMOBUS/Modbus register.

Default: 0

No.

(Addr. Hex)

Name

Description

Values

EtherNet_IM_E_conditional.fm 34 ページ 2012年10月31日 水曜日 午後12時53分