10 bacnet objects supported – Yaskawa BACnet MS/TP User Manual
Page 38
Object ID
Object Name
Modbus
Address
Active Text
Inactive
Text
PV Access
BV13
RUN-STOP
0020H:bit 0
RUN
OFF
R
BV14
REV-FWD
0020H:bit 1
REV
FWD
R
BV15
READY
0020H:bit 2
READY
OFF
R
BV16
FAULT
0020H:bit 3
FAULTED
OFF
R
BV17
Data Set Error
0020H:bit 4
ERROR
OFF
R
BV18
Overcurrent – Gnd Fault
0021H:bit 0
OC-GF
OFF
R
BV19
Main Ckt Overvoltage
0021H:bit 1
OV
OFF
R
BV20
Drive Overload
0021H:bit 2
OL2
OFF
R
BV21
Drive Overheat
0021H:bit 3
OH1-OH2
OFF
R
BV22
Fuse Blown
0021H:bit 5
PUF
OFF
R
BV23
PI Feedback Loss
0021H:bit 6
FBL
OFF
R
BV24
External Fault
0021H:bit 7
EF0-EF
OFF
R
BV25
Hardware Error
0021H:bit 8
CPF
OFF
R
BV26
Mtr Ovrld-OvrTorque
0021H:bit 9
OL1-OL3
OFF
R
BV27
Overspeed
0021H:bit 10
OS-DEV
OFF
R
BV28
Main Ckt Undervoltage
0021H:bit 11
UV
OFF
R
BV29
MCU, Cntl Pwr Sy Err
0021H:bit 12
UV1-2-3
OFF
R
BV30
Output Phase Loss
0021H:bit 13
LF
OFF
R
BV31
Communication Error
0021H:bit 14
CE
OFF
R
BV32
Operator Disconnect
0021H:bit 15
OPR
OFF
R
BV33
Operating
002CH:bit 0
OPERATING
OFF
R
BV34
Zero Speed
002CH:bit 1
ON
OFF
R
BV35
Frequency Agree
002CH:bit 2
ON
OFF
R
BV36
Desired Freq Agree
002CH:bit 3
ON
OFF
R
BV37
Frequency Detect 1
002CH:bit 4
ON
OFF
R
BV38
Frequency Detect 2
002CH:bit 5
ON
OFF
R
BV39
Drv Startup Complete
002CH:bit 6
ON
OFF
R
BV40
Low Voltage Detect
002CH:bit 7
ON
OFF
R
BV41
Base Block
002CH:bit 8
ON
OFF
R
BV42
Frequency Ref Mode
002CH:bit 9
COM
LOCAL
R
BV43
Run Command Mode
002CH:bit 10
COM
LOCAL
R
BV44
Overtorque Detect
002CH:bit 11
ON
OFF
R
BV45
Frequency Refer Lost
002CH:bit 12
ON
OFF
R
BV46
Retry Error
002CH:bit 13
ON
OFF
R
10 BACnet Objects Supported
38
YASKAWA TOEP YEACOM 08A A1000 Option BACnet MS/TP SI-B3 Installation & Technical Manual