Installing and Configuring the Module

MVI56-DFCMR ♦ ControlLogix Platform

DF1 Interface Module with Reduced Data Block

ProSoft Technology, Inc.

Page 27 of 113

October 20, 2008

2.2 Configuration

Data

This section contains listings of the MVI56-DFCMR module's database that are
related to the module's configuration. This data is available to any node on the
network and is read from the ControlLogix processor when the module first
initializes. Additionally, this section contains the miscellaneous status data and
command control database layout.

2.2.1 Backplane

Setup

Register Content

Description

5000

Write Start Reg

Not used in this version of the software

5001

Write Reg Count

Not used in this version of the software

5002

Read Start Reg

Not used in this version of the software

5003

Read Reg Count

Not used in this version of the software

5004 Backplane

Fail

This parameter specifies the number of successive
transfer errors that must occur before the
communication ports are shut down. If the parameter
is set to 0, the communication ports will continue to
operate under all conditions. If the value is set larger
than 0 (1 to 65535), communications will cease if the
specified number of failures occur.

5005

Error Status Pointer

This parameter specifies the register location in the
module's database where module status data will be
stored. If a value less than 0 is entered, the data will
not be stored in the database. If the value specified is
in the range of 0 to 4940, the data will be placed in
the user data area.

5006 to 5009

Spare

2.2.2 Port 1 Setup

Register Content

Description

5010 Enable

This parameter is used to define if this port will be
utilized. If the parameter is set to 0, the port is
disabled. A value of 1 will enable the port.

5011 Type

This parameter defines if the port will emulate a
master or slave device. Enter 0 to emulate a master
device and 1 to emulate a slave device.

5012

Local Station ID

This parameter specifies the local station ID for all
DF1 messages sent from this master port. A value of
255 is not permitted as this is the broadcast address.
Enter a value in the range of 0 to 254.

5013

Protocol

0=full duplex, 1=half-duplex

5014 Termination

Type

This parameter specifies the error checking for all
DF1 messages. 0=BCC, 1=CRC