Fan performance data, Unit electrical data – Envision Peripherals Water-Furnace IM1609 10 User Manual

Page 20

Advertising
background image

19

ENVISION CONSOLE INSTALLATION MANUAL

Fan Performance Data

Model

CFM

Low Speed

High Speed

09

300

350

12

300

350

15

450

500

18

450

500

Factory settings are in Bold
Air flow values are with dry coil and standard filter.

For wet coil performance first calculate the face velocity of the air coil
(Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for
velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300
fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg.

Unit Electrical Data

Model

Rated

Voltage

Voltage

Min/Max

Compressor

Fan

Motor

FLA

Total

Unit
FLA

Min

Circ

Amp

Max

Fuse/
HACR

MCC

RLA

LRA

09

208-230/60/1

197/253

6.4

4.1

21.0

0.50

4.6

5.6

10

265/60/1*

238/292

na

4.3

22.0

0.50

4.8

5.9

10

12

208-230/60/1

197/253

7.7

4.9

25.0

0.50

5.4

6.7

10

265/60/1*

238/292

na

5.3

22.0

0.50

5.8

7.1

10

15

208-230/60/1

197/253

9.2

5.9

29.0

0.69

6.6

8.1

10

265/60/1*

238/292

na

5.6

28.0

0.65

6.3

7.7

10

18

208-230/60/1

197/253

10.4

6.7

33.5

0.69

7.3

9.0

15

265/60/1*

238/292

na

7.3

28.0

0.65

8.0

9.8

15

HACR circuit breaker in USA only
* RLA determine per UL1995 test procedure and not from compressor rating.