Fan performance data, Unit electrical data – Envision Peripherals Water-Furnace IM1609 10 User Manual
Page 20
19
ENVISION CONSOLE INSTALLATION MANUAL
Fan Performance Data
Model
CFM
Low Speed
High Speed
09
300
350
12
300
350
15
450
500
18
450
500
Factory settings are in Bold
Air flow values are with dry coil and standard filter.
For wet coil performance first calculate the face velocity of the air coil
(Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for
velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300
fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg.
Unit Electrical Data
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
09
208-230/60/1
197/253
6.4
4.1
21.0
0.50
4.6
5.6
10
265/60/1*
238/292
na
4.3
22.0
0.50
4.8
5.9
10
12
208-230/60/1
197/253
7.7
4.9
25.0
0.50
5.4
6.7
10
265/60/1*
238/292
na
5.3
22.0
0.50
5.8
7.1
10
15
208-230/60/1
197/253
9.2
5.9
29.0
0.69
6.6
8.1
10
265/60/1*
238/292
na
5.6
28.0
0.65
6.3
7.7
10
18
208-230/60/1
197/253
10.4
6.7
33.5
0.69
7.3
9.0
15
265/60/1*
238/292
na
7.3
28.0
0.65
8.0
9.8
15
HACR circuit breaker in USA only
* RLA determine per UL1995 test procedure and not from compressor rating.
4/8/08