Envision console controls – Envision Peripherals Water-Furnace IM1609 10 User Manual

Page 35

Advertising
background image

34

ENVISION CONSOLE INSTALLATION MANUAL

Envision Console Controls

LOG_IN REQUIRED

User : <= maint =>
Code : 5667

Maint

Maintenance

MinClgSetpt

60.0 ºF

MaxHtgSetpt 89.9 ºF
W Coil LoLim1 30.0 ºF
W Coil LoLim2 15.0 ºF
TmpOccTime 120 min
Rev Vlv Default Heating
BO5 Mode Network
CompStrtDly 90 sec
SpaceT Offset -1 ºF
DehumEnaDis Dis
Acc1 Action On Comp
Acc2 Action On Fan

SW1

OFF

SW2

OFF

SW3

ON

SW4

OFF

SW5

OFF

SW6

OFF

SW7

ON

SW8

OFF

SW9

OFF

SW10

ON

SW11

OFF

SW12

OFF

ECM

ALARM SUMMARY

^/High Pressure

Alarms

Press right arrow key

one time from

Maintenance Menu

No more than three

speeds should be “ON”

at one time

Alarm

#Events

Condensate

0

Hi Pressure

0

Low Pressure

0

Low Temp

0

Bad Sensor

0

Alm-History

NOTE: This FX10 application implements an alarm history which is reset
only by cycling power . This history shows on the Alm-History page. Any
alarm showing 4+ events has occurred more than 4 times.

Alarm lock-outs are reset by cycling power, by pressing the “ESC” and
Return keys simultaneously for a minimum of 15 seconds, or by
commanding the nviAlarmReset over the BAS network.

Test mode is enabled by holding the ‘Esc’ and Down Arrow simultaneously
for a minimum of 15 seconds and releasing. Test mode times out after 30
minutes, and may also be ended by pressing ‘ESC’ and Up Arrow
simultaneously and releasing . Test Mode bypasses the On Delay (90 sec)
and Random Start timers for quicker troubleshooting. It also allows cycling
the reversing valve without compressor shutdown.