Envision console controls – Envision Peripherals Water-Furnace IM1609 10 User Manual
Page 35
34
ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls
LOG_IN REQUIRED
User : <= maint =>
Code : 5667
Maint
Maintenance
MinClgSetpt
60.0 ºF
MaxHtgSetpt 89.9 ºF
W Coil LoLim1 30.0 ºF
W Coil LoLim2 15.0 ºF
TmpOccTime 120 min
Rev Vlv Default Heating
BO5 Mode Network
CompStrtDly 90 sec
SpaceT Offset -1 ºF
DehumEnaDis Dis
Acc1 Action On Comp
Acc2 Action On Fan
SW1
OFF
SW2
OFF
SW3
ON
SW4
OFF
SW5
OFF
SW6
OFF
SW7
ON
SW8
OFF
SW9
OFF
SW10
ON
SW11
OFF
SW12
OFF
ECM
ALARM SUMMARY
^/High Pressure
Alarms
Press right arrow key
one time from
Maintenance Menu
No more than three
speeds should be “ON”
at one time
Alarm
#Events
Condensate
0
Hi Pressure
0
Low Pressure
0
Low Temp
0
Bad Sensor
0
Alm-History
NOTE: This FX10 application implements an alarm history which is reset
only by cycling power . This history shows on the Alm-History page. Any
alarm showing 4+ events has occurred more than 4 times.
Alarm lock-outs are reset by cycling power, by pressing the “ESC” and
Return keys simultaneously for a minimum of 15 seconds, or by
commanding the nviAlarmReset over the BAS network.
Test mode is enabled by holding the ‘Esc’ and Down Arrow simultaneously
for a minimum of 15 seconds and releasing. Test mode times out after 30
minutes, and may also be ended by pressing ‘ESC’ and Up Arrow
simultaneously and releasing . Test Mode bypasses the On Delay (90 sec)
and Random Start timers for quicker troubleshooting. It also allows cycling
the reversing valve without compressor shutdown.
MUI Menu Navigation for Single Compressor - Envision Water-to-Air