Microprocessor Control (cont.)

Heat, 3rd Stage (Y1,Y2,W) Dual Capacity Units

The hot water pump is de-energized which directs all heat

to satisfy the thermostat. The 1st stage of resistance heat is

energized 10 seconds after “W” input, and with continuous 3rd

stage demand, the additional stages of resistance heat engage

sequentially every 5 minutes.

Emergency Heat (W only)

The fan is started on high speed, and the first stage of

resistance heat is energized 10 seconds after the "W" input.

Continuing demand will engage the additional stages of

resistance heat sequentially every 2 minutes.

Cooling Operation

In all cooling operations, the reversing valve directly

tracks the “O” input. Thus, anytime the “O” input is present,

the reversing valve will be energized.
Cool, 1st Stage (Y1,O)

The blower motor and hot water pump are started immediately,

the loop pump(s) is energized 5 seconds after the “Y1” input is

received. The compressor will be energized (on low capacity for

Dual Capacity units) 10 seconds after the “Y1” input. The ECM

blower will shift from low to medium speed 15 seconds after the

“Y1” input (85% of medium speed if in dehumidification mode).
Cool, 2nd Stage (Y1, Y2, O) Single Speed Units

The fan changes to high speed (85% of high speed if in

dehumidification mode) 15 seconds after the “Y2” input (ECM only).
Cool, 2nd Stage (Y1, Y2, O) Dual Capacity Units

The second stage compressor will be activated 5 seconds

after receiving a “Y2” input as long as the minimum first stage

compressor run time of 1 minute has expired. The ECM blower

changes to high speed 15 seconds after the “Y2” input (85% of

high speed if in dehumidification mode). The Comfort Alert will

delay the second stage compressor until 5 seconds after it

receives a “Y2” from the board.

Fan (G only)

The fan starts on low speed (PSC ON). Regardless of fan

input “G” from thermostat, the fan will remain on low speed for 30

seconds at the end of each heating, cooling or emergency heat

cycle.

A DIP switch on the Envision control allows field selection of

15% reduced fan speeds for cooling in the dehumidification mode

or medium and high fan speeds for cooling in the normal mode.

Note: Fan speed can change automatically only with an ECM Motor.

ECM2 Airflow Selection DIP Switches (SW1)

A 12-position DIP switch package on the Envision control

allows the airflow levels to be set for low, medium and high speed.

(Refer to the ECM Blower Table on page 15.)

Only three of the DIP switches can be in the “on” position.

The first “on” switch (the lowest position number) determines the

“low speed fan” setting. The second “on” switch determines the

“medium speed fan” setting, and the third “on” switch determines

the “high speed fan” setting, (see page 15).

Lockout Conditions

During lockout mode, the appropriate unit and thermostat

lockout LEDs will illuminate. The compressor, loop pump, hot

water pump, and accessory outputs are de-energized. Unless the

lockout is caused by an ECM2 low RPM fault, the fan will continue

to run on low speed. If the thermostat calls for heating, emergency

heat operation will occur.

Comfort Alert lockouts cannot be reset at the thermostat.

All other lockout modes can be reset at the thermostat after

turning the unit off, then on, which restores normal operation but

keeps the unit lockout LED illuminated. Interruption of power to

the unit will reset a lockout without a waiting period and clear all

lockout LEDs.

High Pressure

This lockout mode occurs when the normally closed safety

switch is opened momentarily (set at 600 PSI).

Low Pressure

This lockout mode occurs when the normally closed low

pressure switch is opened for 30 continuous seconds (set at 40 PSI).

A low pressure fault may also be indicated when a Comfort Alert

lockout has occurred.

Freeze Sensing (Water Flow)

This lockout mode occurs when the freeze thermistor

temperature is at or below the selected freeze sensing point (well

30°F or loop 15°F) for 30 continuous seconds.

Condensate Overflow

This lockout mode occurs when the condensate overflow

level has been reached for 30 continuous seconds.

Fan RPM

The control board monitors fan RPM to sense operation.

This lockout mode occurs if the fan RPM falls below the low RPM

limit (100 RPM) for 30 continuous seconds (ICM only).