Installing horizontal units – Envision Peripherals R-410A User Manual

Page 5

Advertising
background image

5

ENVISION RESIDENTIAL INSTALLATION MANUAL

Installing Horizontal Units

Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket

prior to setting the unit in place. Horizontal units are available with side or end discharge. Horizontal units are normally sus-

pended from a ceiling by six 3/8-inch diameter threaded rods. The rods are usually attached to the unit by hanger bracket

kits furnished with each unit.

Lay out the threaded rods per the dimensions below. Assemble the hangers to the unit as shown. Securely tighten the

brackets to the unit using the weld nuts located on the underside of the bottom panel. When attaching the hanger rods to

the bracket, a double nut is required since vibration could loosen a single nut. To allow filter access, one bracket on the filter

side should be installed 180° from the position shown in the figure below. The unit should be pitched approximately 1/4-inch

towards the drain in both directions to facilitate the removal of condensate. Use only the bolts provided in the kit to attach

hanger brackets. The use of longer bolts could damage internal parts.

Some residential applications require the installation of horizontal units on an attic floor. In this case, the unit should

be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible

condensate overflow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base

isolated from the ceiling joists by additional layers of vibration absorbing material.

Insulate supply

plenum and use

at least one 90

elbow to

reduce noise

Electrical

Disconnect

Flexible Duct

Collar

Threaded Rods

Line Voltage

Ball V

alves

Hose

Kits

To Line

Power

To

Thermostat

Hanging

Brackets

(Included)

Building Water Loop

O

Figure 2: Horizontal Unit Mounting

CAUTION: Do not use rods smaller than 3/8-inch diameter since they may not be strong enough to

support the unit. The rods must be securely anchored to the ceiling.

Figure 3: Hanger Location and Assembly

C

F

B

Air Coil

Air Coil

D

E

A

Vibration Isolator

Washer

Hex Nuts
(not supplied)

Bolt and
Lockwasher

3/8

Threaded Rod

(not supplied)

Model

A

B

C

D

E

F

022 - 030

24.8

27.8

27.8

27.8

63.4

21.1

38.1

25.3

1.1

036 - 038

72.4

24.1

43.1

29.3

1.1

042 - 049

77.4

24.1

48.1

29.3

1.1

060 - 072

82.4

24.1

53.1

29.3

1.1