Factory Settings

35

7.2

Liebert DS - Local Node Settings for Multiple Cards

If you use two cards of the same type with the Liebert DS, you will need to change the local node set-

ting of one card. These steps apply only when both cards are the same type, either:

• Two Liebert IntelliSlot Web cards (P/N IS-WEBLBDS)

or

• Two Liebert IntelliSlot 485 cards (P/N IS-485LBDS)

Terminal Emulation (Serial or TCP/IP Connection) / Telnet

To access local node settings:
1. Choose Factory Settings from the Main Menu.
2. Choose Advanced Communication Settings from the Factory

Settings Menu.

3. Choose Local Node Settings from the Advanced

Communication Settings Menu.

4. Choose Node 1 from the Local Node Settings Menu, then use the

following guide to make changes.
If there are two Liebert IntelliSlot Web cards or two Liebert

IntelliSlot 485 cards, you must change the address of one card

(see Table 22):

• For the Liebert IntelliSlot Web card, the default address is 1.

For two Web cards, set the address of the second card to 2.

• For the Liebert IntelliSlot 485 card, the default address is 2.

For two 485 cards, set the address of the second card to 1.

Table 22

Factory default MAC addresses

Liebert IntelliSlot Card

Part Number

Factory Default

MAC Address

Set Node 1 Address

of Second Card to:

Liebert IntelliSlot Web Card-LBDS

IS-WEBLBDS

0x01

2

Liebert IntelliSlot 485 Card-LBDS

IS-485LBDS

0x02

1

Liebert DS

Factory Settings Menu
----------------------
1: Advanced Communication

Settings

2: Reset to Factory Defaults

<ESC>: Cancel menu level

Please select a key ?>

Liebert DS

Advanced Communication Settings
Menu
--------------------------------
1: Local Node Settings
2: Managed Device Settings
2: Reset to Default

<ESC>: Cancel menu level

Please select a key ?>

Liebert DS

Local Node Settings Menu
-------------------------
1: Node ID: 1
2: Communication Rate: 38400
3: Maximum Master Address: 3
4: Maximum Retry Count: 5
5: Retry Interval(sec): 5

<ESC>: Cancel menu level

Please select a key ?>