LCX9000 Liquid-Cooled Drives User Manual

MN04005001E

For more information visit: www.EatonElectrical.com

5-9

January 2007

You can return to the Main menu any time by pressing Menu Button Left for 1 to 2 seconds.

The basic application package includes seven applications with different sets of parameters.
You will find the parameter lists in the application manual.

Once in the last parameter of a parameter group, you can move directly to the first parameter
of that group by pressing Browser button up.

See the diagram for parameter value change procedure in Figure 5-6.

Figure 5-6: Parameter Value Change Procedure

Keypad Control Menu (M3)

In the Keypad Control Menu, you can choose the control place, edit the frequency reference
and change the direction of the motor. You can enter the submenu level by pressing Menu
Button Right.

Table 5-7: Keypad Control Parameters, M3

Basic parameters

P1

P18

Parameters

G1

G8

Min Frequency

13.95 Hz

Min Frequency

13.95 Hz

Min Frequency

14.45 Hz

Input signals

G1

G8

Code Parameter

Min.

Max.

Unit Default Cust. ID

Note

P3.1

Control place

1

3

1

125 1 = I/O terminal

2 = Keypad
3 = Fieldbus

P3.2

Keypad reference Par. 2.1.1 Par. 2.1.2 Hz

P3.3

Direction
(on keypad)

0

1

0

123 0 = Forward

1 = Reverse

R3.4

Stop button

0

1

1

114 0 = Limited function of Stop

button

1 = Stop button always

enabled