General, Venting – Lochinvar Sunc Condensing Boiler 1.3 User Manual

Page 17

Advertising
background image

17

2

General

venting

(continued)

Installation & Operation Manual

Materials

Air inlet pipe materials:

The air inlet pipe(s) must be sealed. Choose acceptable
combustion air inlet pipe materials from the following list:

PVC, CPVC, Polypropylene or ABS

Dryer Vent or Sealed Flexible Duct (not recommended

for rooftop air inlet)

Galvanized steel vent pipe with joints and seams sealed as

specified in this section.

Type “B” double-wall vent with joints and seams sealed as

specified in this section.

AL29-4C, stainless steel material to be sealed to

specification of its manufacturer.

*Plastic pipe may require an adapter (not provided) to
transition between the air inlet connection on the appliance
and the plastic air inlet pipe.

ƽ WARNING Using air intake materials other than

those specified can result in personal
injury, death or property damage.

NOTICE

The use of double-wall vent or insulated
material for the combustion air inlet pipe is
recommended in cold climates to prevent
the condensation of airborne moisture in
the incoming combustion air.

Sealing of Type “B” double-wall vent material or galvanized
vent pipe material used for air inlet piping on a sidewall or
vertical rooftop Combustion Air Supply System:
a. Seal all joints and seams of the air inlet pipe using either

Aluminum Foil Duct Tape meeting UL Standard 723 or

181A-P or a high quality UL Listed silicone sealant such as

those manufactured by Dow Corning or General Electric.

b. Do not install seams of vent pipe on the bottom of
horizontal

runs.

c. Secure all joints with a minimum of three (3) sheet metal

screws or pop rivets. Apply Aluminum Foil Duct Tape or

silicone sealant to all screws or rivets installed in the vent

pipe.
d. Ensure that the air inlet pipes are properly supported.

The PVC, CPVC, or ABS air inlet pipe should be cleaned and
sealed with the pipe manufacturer’s recommended solvents
and standard commercial pipe cement for the material used.
The PVC, CPVC, ABS, Dryer Vent or Flex Duct air inlet pipe
should use a silicone sealant to ensure a proper seal at the
appliance connection and the air inlet cap connection. Dryer
vent or flex duct should use a screw type clamp to seal the vent
to the appliance air inlet and the air inlet cap. Proper sealing
of the air inlet pipe ensures that combustion air will be free of
contaminants and supplied in proper volume.

When a sidewall or vertical rooftop combustion air supply
system is disconnected for any reason, the air inlet pipe must
be resealed to ensure that combustion air will be free of
contaminants and supplied in proper volume.

ƽ DANGER

Failure to properly seal all joints and seams
as required in the air inlet piping may
result in flue gas recirculation, spillage
of flue products and carbon monoxide
emissions causing severe personal injury
or death.

Advertising