Maintenance maintenance and annual startup, Service technician, Owner maintenance – Lochinvar Sunc Condensing Boiler 1.3 User Manual

Page 57

Advertising
background image

57

Installation & Operation Manual

11

Maintenance

Maintenance and annual startup

Table 11A Service and Maintenance Schedules

Service technician

(see the following pages for instructions)

General:

• Address reported problems, if any

• Inspect interior; clean and vacuum if

necessary;

• Clean condensate trap and fill with fresh

water

Check for leaks (water, gas, flue,

condensate)

• Verify flue and air lines in good condition

and sealed tight

• Check system water pressure/system

piping/expansion

tank

• Check control settings

• Check ignition and flame sense

electrodes (sand off any deposits; clean

and

reposition)

• Check wiring and connections

Perform start-up checkout and

performance verification per Section 9.

• Flame inspection (stable, uniform)

• Flame signal (at least 10 microamps at

high fire)

Clean the heat exchanger if flue

temperature is more than 54°F (30°C)

above return water temperature.


Test low water flow conditions

(reference the SYNC Service Manual).

If combustion or performance
indicate need:

• Clean heat exchanger


Remove and clean burner using

compressed air only

• Clean the blower wheel

ANNUAL START-UP

Owner maintenance

(see the SYNC User’s Information Manual for

instructions)

Daily

• Check boiler area

Check pressure/temperature

gauge

Monthly

• Check vent piping

• Check air piping

• Check air and vent termination

screens


• Check relief valve

• Check condensate drain system

Check automatic air vents

Every

6 months

• Test low water cutoff

• Reset button (low water cutoff)


• Check boiler piping (gas and

water)

for

leaks

• Operate relief valve

End

of season

months



• Shut boiler down (unless boiler

used for domestic hot water)