Condensate disposal

Condensate drain

1. This boiler is a high efficiency appliance that produces

condensate.

2. The rear of the boiler has a 1/2 inch (12.7 mm) PVC

union for connection of a 1/2 inch (12.7 mm) PVC pipe
(FIG. 8-1).

3. Slope condensate tubing down and away from the boiler

into a drain or condensate neutralizing filter. Condensate
from the SYNC will be slightly acidic (typically with a pH
from 3 to 5). Install a neutralizing filter if required by
local codes.

A Neutralizer Kit (FIG. 8-1) is available from the factory
(KIT3046).

4. Install the 1/2 inch (12.7 mm) PVC tee assembly (shipped

with the unit) as shown in FIG. 8-1.

5. Leave the top of the 1/2 inch (12.7 mm) tee OPEN. This

is needed as a vacuum break.

6. Do not expose condensate line to freezing temperatures.

Use materials approved by the authority
having jurisdiction. In the absence of
other authority, PVC and CPVC pipe
must comply with ASTM D1785 or D2845.
Cement and primer must comply with
ASME D2564 or F493. For Canada use
CSA or ULC certified PVC or CPVC pipe,
fittings, and cement.

7. A condensate removal pump is required if boiler is below

drain. When installing a condensate pump, select one
approved for use with condensing boilers and furnaces.
The pump should have an overflow switch to prevent
property damage from condensate spillage. The switch
should be wired to the auxiliary device proving switch
terminals on the low voltage connection board.

NOTICE

NOTICE

To allow for proper drainage on large
horizontal runs, a second line vent may
be required and tubing size may need to
increase to 1 inch (25 mm).

The condensate line must remain
unobstructed, allowing free flow of
condensate. If condensate is allowed to
freeze in the line or if the line is obstructed
in any other manner, condensate can exit
from the boiler tee, resulting in potential
water damage to property.

NEUTRALIZER KIT

1/2" (12.7 mm) PVC UNION

(FACTORY SUPPLIED)

1/2" (12.7 mm) PVC TEE ASSEMBLY

(FACTORY SUPPLIED)

FLOOR DRAIN

OR DRAIN PAN

Figure 8-1 Condensate Disposal