2.3.2 Connecting to External Panel Boards

The following instructions are also shipped attached to the rear of the unit.

INPUT CABLING AND PROTECTION

Table Below Applies to 4-16kVA Scalable Systems:

Stand-alone UPS or
UPS equipped with a Maintenance Bypass Cabinet

Max. System

Load Rating

Input Voltage – 200/210VAC

Max. Current
in UPS mode

Recommended

Input Protection

Circuit Breaker

4kVA

18 amps

50 amps

8kVA

36 amps

50 amps

12kVA

53 amps

75 amps

16kVA

70 amps

100 amps

Terminal

Block

Details

Maximum: 35mm

2

(2AWG)

Minimum: 16mm

2

(6AWG)

Torque Rating: 2.5-3.0Nm (22-26in/lbs)