0 specifications, 1 product warranty registration, Pecifications – Liebert NfinityTM User Manual

Page 41: Product warranty registration

Advertising
background image

Specifications

37

6.0

S

PECIFICATIONS

6.1

Product Warranty Registration

To register for warranty protection:

• Visit the Quick Links section of our Web site at:

http://www.liebert.com

• Click on Product Warranty Registration and fill in the form.

If you have any questions, please contact us at:

US: 800-222-5877

Outside the US: 614-841-6755

[email protected]

General & Environmental

Units

Configuration

Unit Rating

kVA

4

8

12

16

kW

2.8

5.6

8.4

11.2

Compliant Safety Standards

UL 1778; c-UL

Conducted and Radiated EMC Levels

FCC Part 15, Class A

Compliant Immunity Standards

IEEE C62.41, Category B

Mechanical

Units

8 Bay

12 Bay

Dimensions

Width

in (mm)

20 (508)

20 (508)

Depth

28 (711)

28 (711)

Height

40 (1016)

54 (1372)

Environmental

Units

Operating Temperature (max)

F (C)

32° - 104° (0° - 40°)

Relative Humidity

%

0-95% non-condensing

10,000 (3,000)

Maximum operating altitude

ft. (m)

Nominal heat dissipation

BTU/Hr

1,062

2,124

3,186

4,248

Acoustic noise level

dBA

<62 @ 1 meter

Input Data

Units

Nominal input voltage

VAC

200 or 210

Minimum Voltage

Range (Typical)

Operating voltage range is variable based on output loading percentages

% UPS Load

Input Voltage

80 – 100%

170 VAC

60 – 80%

144 VAC

30 – 60%

127 VAC

0 – 30%

110 VAC

Power factor

Cos Ø

>.98

Input frequency (nominal)

Hz

50 or 60

Input frequency range

Hz

40-70

Battery Module

Units

Number of lead acid batteries

10

Number of battery cells

60

Maximum charge current (full load)

A

3

Nominal Voltage

VDC

120

Recharge Time

Hrs

Typically 6 (to 90% capacity)

Output Data

Units

Output voltage

VAC

210/105

Voltage regulation

%

±3

Voltage stability (100% step load)

%

±7

Recovery time

msec

96

Voltage distortion

%

<3 THD, linear load

<7 THD, non-linear load

Output frequency

Hz

60

Efficiency at 100% load

%

89

Output overload capability

%

110 - 125% for 10 min

126-150% for 10 sec

151 - 200% for 2 cycles

Advertising