Liebert GXTTM User Manual

Page 19

Advertising
background image

17

AIRFLOW

DISSIPATION

OUTPUT

RATING

INPUT CURRENT

Amps max

Cfm

m

3

h

Watts

K Btu/hr

VA

Watts

Including mains

variation/battery charge

130

221

504

1.7

6000

4200

GXT6000 = 33 amps

270

459

840

2.8

10000

7000

GXT10000= 54 amps

ELECTRICAL INSTALLATION CONSIDERATIONS
This UPS must be installed by competent electrical personnel and wired in
accordance with local/national electrical codes.

The following information is provided for your guidance.

On start-up, the UPS will take a half cycle inrush current of up to 3 times the
rated current. This must be taken into account when selecting the overload
protection device at the input mains supply distribution point. To avoid random
tripping on start-up, we recommend that the input mains supply be protected with
an MCB capable of withstanding this initial inrush. An MCB specified as being
“TYPE 4” (British standard) or “CURVE D” (IEC standard) is suitable for this
purpose.

The mains input supply cable must be connected to the UPS via a wall mounted
double pole circuit breaker, rated to carry the current in table 1 and be capable of
breaking the maximum prospective short circuit current of this branch circuit. The
breaker is to be mounted within two metres of the UPS and be readily accessible
to the operator.

WARNING

This UPS does not incorporate automatic backfeed protection.
A warning label must be fitted to all primary power isolators stating:
ISOLATE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON
THIS CIRCUIT.

CAUTION

This UPS is fitted with EMC suppression filters. Earth leakage
exceeds 35mA. Transient and steady state earth leakage currents,
which may occur when starting the UPS, should be taken into
account when selecting instantaneous RCCB or RCCD devices. Note
also that the earth leakage currents of the load will be carried by this
RCCB or RCCD.

WARNING

HIGH EARTH LEAKAGE CURRENT- EARTH CONNECTION IS
ESSENTIAL BEFORE CONNECTING THE MAINS SUPPLY. Earth in
accordance with local electrical codes.

Advertising