Liebert GXTTM User Manual

Page 28

Advertising
background image

26

SPECIFICATIONS

MODEL NUMBER

GXT6000T-230X

GXT10000T-230X

MODEL RATING VA/W (max)

6000 / 4200

10000 / 7000

DIMENSIONS: mm (in)

Unit

W x D x H

260 x 555 x 803

(10.5 x 22.0 x 31.5)

340 x 650 x 960

(13.5 x 25.5 x 38.0)

Shipping

W x D x H

400 x 850 x 1065

(16.0 x 33.5 x 42.0)

510 x 840 x 1235

(20.0 x 33.0 x 48.5)

WEIGHT: kg (lbs)

Unit

139 (306)

244 (538)

Shipping

170 (374)

284 (626)

Input/Output Connections

Hardwire terminal block

INPUT AC PARAMETERS

Voltage Range (typical)

230 VAC nominal; variable based upon output load

100% - 90% Loading

186 VAC to 280 VAC; ±5.0 VAC

90% - 70% Loading

159 VAC to 280 VAC; ±5.0 VAC

70% - 30% Loading

139 VAC to 280 VAC; ±5.0 VAC

30% - 0% Loading

119 VAC to 280 VAC; ±5.0 VAC

Frequency

46.6 – 52.4 Hz or 57.1 - 62.9 Hz; auto sensing

OUTPUT AC PARAMETERS

Voltage

208/220/230/240 VAC (switch selectable); ±7%

Frequency

50 Hz or 60 Hz; auto sensing

Waveform

Sinewave

Main Mode Overload

200% for 8 cycles; 130% for 10 seconds with transfer to

bypass

BATTERY PARAMETERS

Type

Valve-regulated, nonspillable, lead acid

Qty. x Voltage x Rating

20 x 12V x 7.0 Ah

40 x 12V x 7.0 Ah

Back-up Time

7 min. minimum

10 min. minimum

Recharge Time

(Internal Batteries Only)

7 hours to 95% capacity after full discharge into 100%

load

ENVIROMENTAL

Operating Temperature

0° C to +40° C (+32° F to +104° F)

Storage Temperature

-15° C to +50° C (+5° F to +122 °F)

Relative Humidity

0% to 95%, non-condensing

Operating Elevation

Up to 3000 m (10,000 ft.) at 40° C without derating

Storage Elevation

15.000 m (50,000 ft.) maximum

Audible Noise

<55 dB ”A” at 1 metre

<65 dB ”A” at 1 metre

AGENCY

Safety

EN50091-1-1; TUV/GS Listed; CE Low Voltage Directive

EMI/EMC

EN50091-2, Class A; CE EMC Directive

Immunity

IEC 801-2, Level 4 / IEC 801-3,

Level 3 / IEC 801-4, Level 4 / IEC801-5,Level 3

Advertising