Mounting

Radar Tank Gauge

14

Installation and Operations Manual

3.3.2

Engineering tips

Measuring conditions
• The measuring range starts at the bottom end of the stilling well.
• In case of media with a low dielectric constant (groups A and B), the pipe end can be

visible through the medium at low levels. In order to guarantee the required accuracy

in these cases, it is recommended to position the zero-point at a distance C above the

tank bottom (see Fig.).

• In applications with planar or parabolic antennas, especially for media with low

dielectric constants (see page 15), the end of the measuring range should not be closer

than 1 m (40”) to the flange.

• For overspill protection, it is possible to define a safety distance (SD) additionally to

the blocking distance (BD).

• This safety distance (SD) is set to 0.5 m (20") by default and generating an alarm in

case the level rises inside the safety distance.

• Distance B defined the smallest recommended measurement range.
• Depending on its consistence, foam can either absorb microwaves or reflect them off

the foam surface. Measurement is possible under certain conditions.

Behaviour if measuring range is exceeded

The behaviour in case of the measuring range being exceeded can be freely set: the

default setting is a current of 22 mA and the generation of a digital warning (E681).

reference: flange / BD

(see picture)

reference: antenna tip

(see picture)

recommended additional settings

Blocking

distance

Safety

distance

BD [m / ft]

SD [m / ft]

A [mm / inch]

B [m / ft]

C [mm / inch]

7532 RTG (planar)

1 / 3.28

0.5 / 1.6

1000 / 40

0.5 / 1.64

150…300 /

6…12

L0

0-FM

R5

3xxx-17

-00

-0

0-en-00

8

BD

SD

A

100%

0%

B

C

max. level