Function "medium property" (003) – Lightning Audio 7532 User Manual

Page 50

Advertising
background image

Commissioning

Radar Tank Gauge

50

Installation and Operations Manual

Function "medium property" (003)

This function is used to select the dielectric constant.

Selection:
unknown
• < 1.9
• 1.9 ... 4
• 4 ... 10
• > 10

3)Treat Ammonia NH3 as a medium of group A, i.e. always use a stilling well.

E

+

Product class

DK (

e

r)

Examples

A

1,4 … 1,9

non-conducting liquids, e.g. liquefied gas

3)

B

1,9 … 4

non-conducting liquids, e.g. benzene, oil, toluene, …

C

4 … 10

e.g. concentrated acids, organic solvents, esters, aniline,

alcohol, acetone, …

D

> 10

conducting liquids, e.g. aqueous solutions, dilute acids and

alkalis