Sidewall direct

venting

Vent/air termination – sidewall

Follow instructions below when
determining vent location to avoid
possibility of severe personal injury, death,
or substantial property damage.

A gas vent extending through an exterior
wall shall not terminate adjacent to a wall
or below building extensions such as eaves,
parapets, balconies, or decks. Failure to
comply could result in severe personal
injury, death, or substantial property
damage.

Installation must comply with local
requirements and with the National
Fuel Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.

ƽ WARNING

ƽ WARNING

NOTICE

ƽ WARNING Do not connect any other appliance to

the vent pipe or multiple boilers to a
common vent pipe. Failure to comply
could result in severe personal injury,
death, or substantial property damage.

Determine location

Locate the vent/air terminations using the following
guidelines:

1. The total length of piping for vent or air must not exceed

the limits given in the General Venting Section on page
19 of this manual.

2. You must consider the surroundings when terminating

the vent and air:
a. Position the vent termination where vapors will
not damage nearby shrubs, plants or air

conditioning equipment or be objectionable.

b. The flue products will form a noticeable plume as

they condense in cold air. Avoid areas where the

plume could obstruct window views.

c. Prevailing winds could cause freezing of

condensate and water/ice buildup where flue

products impinge on building surfaces or plants.

d. Avoid possibility of accidental contact of flue

products with people or pets.

e. Do not locate the terminations where wind eddies

could affect performance or cause recirculation,

such as inside building corners, near adjacent

buildings or surfaces, window wells, stairwells,

alcoves, courtyards, or other recessed areas.

TO BOILER

INTAKE AIR

CONNECTION

FROM BOILER

VENT PIPE

CONNECTION

TERMINATION

PLATE

BIRD SCREEN

GRADE OR

SNOW LINE

12”

MIN

BIRD SCREEN

12” MIN

15” MAX

Do not exceed the maximum lengths of the
outside vent piping shown in FIG. 4-1B.
Excessive length exposed to the outside
could cause freezing of condensate in the
vent pipe, resulting in potential boiler
shutdown.

Figure 4-1B Alternate PVC/CPVC Sidewall Termination
of Air and Vent w/Field Supplied Fittings

ƽ WARNING

If using the alternate sidewall termination:

3. The air piping must terminate in a down-turned elbow

as shown in FIG. 4-1B. This arrangement avoids
recirculation of flue products into the combustion air
stream.

4. The vent piping must terminate in an elbow pointed

outward or away from the air inlet, as shown in FIG. 4-1B.

TO BOILER

INTAKE AIR

CONNECTION

FROM BOILER

VENT PIPE

CONNECTION

VENT / AIR

TERMINATION

GRADE OR

SNOW LINE

12"

MIN

12"

MIN

TO

OVER-

HANG

POSSIBLE ORIENTATIONS

Figure 4-1A PVC/CPVC Sidewall Termination of Air and
Vent

Model

Kit Number

Vent Size

55 - 110

KIT30044

2 inch vent

110 - 285

KIT30045

3 inch vent

399

KIT30046

4 inch vent

Table 4A Sidewall Vent Kit

Installation & Operation Manual