Hydronic piping – Lochinvar KNIGHT WH 55 - 399 User Manual

Page 42

Advertising
background image

6

Hydronic piping

Figure 6-7 Multiple Boilers - Single Temperature Zoned with Circulators - DHW Priority

INDIRECT

DHW TANK

BACKFLOW

PREVENTER

PRESSURE

REDUCING VALVE

PRESSURE

GAUGE

ANTI-SCALD

MIXING VALVE

AIR SEPARATOR

EXPANSION

TANK

BALL VALVE

(TYPICAL)

DRAIN POINT

(TYPICAL)

MAKE UP

WATER

ZONE CIRCULATORS

(TYPICAL)

FLOW CHECK

VALVE

(TYPICAL)

BOILER
CIRCULATOR

BOILER 2
(MEMBER 1)

DOMESTIC

HOT WATER

CIRCULATOR

UNION

(TYPICAL)

PRESSURE

RELIEF VALVE

HOT

WATER

OUT

COLD

WATER

IN

BOILER 1
(LEADER)

SYSTEM SUPPLY

SENSOR

TEMPERATURE /

PRESSURE

GAUGE

DRAIN

Y-STRAINER
(RECOMMENDED)
(TYPICAL)

MAY SUBSTITUTE LOW LOSS HEADER

NOT TO EXCEED 4 PIPE DIA OR MAX. OF 12" APART

ZONE #1

ZONE #2 ZONE #3 ZONE #4

Please note that these illustrations are meant to show system piping concept only, the installer is responsible
for all equipment and detailing required by local codes.

NOTICE

42

Installation & Operation Manual

Model

Number of Units

2

3

4

5

6

7

8

Required Pipe Sizes

55

1-1/4" 1-1/2" 1-1/2"

2"

2"

2"

2"

85

1-1/4" 1-1/2"

2"

2"

2"

2-1/2" 2-1/2"

110

1-1/2"

2"

2"

2-1/2" 2-1/2" 2-1/2"

3"

155

2"

2"

2-1/2" 2-1/2"

3"

3"

4"

199

2"

2"

2-1/2"

3"

4"

4"

4"

285

2-1/2" 2-1/2"

3"

4"

4"

4"

5"

399

2-1/2"

3"

4"

4"

5"

5"

5"