Floating point data – Varec 4000 User Manual

Page 62

Advertising
background image

Modbus Implementation

Tank Gauge Transmitter

52

Installation and Operations Manual

9.6.4

The One 32-bit Register Format

Function code 65 (41 Hex) is used to read floating-point registers in this format. An example of a floating-point

register read is shown below with the a temperature of 100.0 degrees is being read from register 1 (0001 Hex).

9.6.5

Floating Point Data

Hexadecimal representation: 42 C8 00 00

Decimal equivalent: 100.00

Function code 66 (42 Hex) is used to write floating-point registers. An example of a floating-point register write is

shown below with the value 100.0 being written into the Advisory High Temperature Alarm Setpoint, register 12 (000C

Hex).

9.6.6

Floating Point Data

Hexadecimal representation: 42 C8 00 00

Decimal equivalent: 100.00

Floating-point registers that are defined as reserved have zero (0) as their value. A write command to a reserved

floating-point register will be ignored.

Host Request
Address

Function

Code

Start

Reg H

Start

RegL

# of

Reg H

# of

Reg L

Error
Check

01

41

00

01

00

01

XX

ATT Response
Address

Function

code

# of

Reg H

# of

Reg L

Data
MSB

Data

Data

Data

LSB

Error

Check

01

41

00

01

42

C8

00

00

XX

Host Request
Address

Function

Code

Start Reg
H

Start Reg
L

# of Reg
H

# of Reg
L

Data

MSB

01

42

00

0C

00

01

42

Data

Data

Data
LSB

Error

Check

C8

00

00

XX

ATT Response
Address

Function

code

# of Reg

H

# of Reg

L

Error
Check

01

03

02

41

XX