Status bit data, Exception responses, 7 status bits – Varec 4000 User Manual

Page 63

Advertising
background image

53

4000

Modbus Implementation

9.7

Status Bits

In the ATT implementation, status bits contain alarms, commands, and status information. The state of a Modbus

status bit is defined as either ON (true) or OFF (false). The ON state is represented by a "1". The status bits may be read

with function code 1 or 2. They may be written one at a time with function code 5 or multiple bits may be written with

function code 15. An example of a read message for bits 2 through 6 as returned by the ATT is shows as follows.

9.7.1

Status Bit Data

Binary representation 1 0010 (bits 6-2)

Bit #2: High Advisory Alarm OFF

Bit #3: High Critical Alarm ON

Bit #4: Unauthorized Mass Movement OFF

Bit #5: Standard Density Alarm OFF

Bit #6: Critical Zone Alarm ON

9.8

Exception Responses

The exception responses returned by the ATT are listed below:

In addition, messages that are received with a parity error, checksum error, or message format error will be ignored.

Host Request
Address

Function

Code

Start Reg
H

Start Reg
L

# of Reg
H

# of Reg
L

Error
Check

01

02

00

02

00

04

XX

ATT Response
Address

Function

code

Byte

Count

Data

Error
Check

01

02

01

12

XX

Exception

Response

Reason

01

Illegal Function

Message is not allowed

02

Illegal Data Address

Data address (bit or register) requested is not defined

03

Illegal Data Value

Data value being written is out of range

04

Busy

During power-up