Optional Interfaces

Tank Gauge Transmitter

62

Installation and Operations Manual

10.5 4000WBFMO

This option can co-exist along side Whessoe Bus™ transmitters, the signal format is a current loop style transmission

signal. Transmitter is user selectable between 1 and 127 with basic baud rates stop and parity bits. The protocol is

referred to as Whessmatic 550, which was widely used by the UK for their Intelligent Tang gauging systems. The ATT

meets and exceeds the requirements of the Whessmatic 550 format because of its redundant dual port capabilities,

and the bipolar signal circuitry design. The advanced circuitry allows the ATT to communicate without error at 9600

baud through 2 data ports simultaneously. A typical transmitter using current loop signal format nominally

communicates at 300 to 1200 baud at maximum.

10.6 4000GMFMO

Basically this is identical to the standard release of the 400048FMO, a MODBUS protocol device communicating over

RS-485 data lines. GSI, a tank gauging systems manufacturer has re-mapped level and temperature integer registers

to non-standard MODBUS locations. This version ATT allows it to co-exist along side GSI transmitters and gauging

systems with response data as expected.